Notice of Violatlions (Current)
NOV Number:
E0020252651
(Pending)
Issue Date:
10/7/2025
Expiration Date:
12/6/2025
View NOV Form
| Tanks |
Violations |
| 4, 5 |
Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Spill bucket inner cover deteriorated - repair or replace |
| 4, 5 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
| 6 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Sump sensor submerged in liquid- repair or replace and submit new test results to OSFM Portal- leave paperwork on site to repairs made to containment. |