Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 3007526
Status: Inactive
Facility Name: Corner View
Address: 2400 7th Avenue Rock Island, IL 61201
County: Rock Island
Property Parcel: 07-36-330-001
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z000362
Green Tag Issue Date: 3/8/2024
Green Tag Expiration Date: 12/31/2026

Owner Details

Owner Name: Get-N-Go, Inc.
Owner Address: 2400 7th Ave. Rock Island, IL 61201
Owner Status: Current Owner
Purchase Date: 4/1/2014
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 3/2/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 3/8/2024 12/31/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0036984 Get-N-Go, Inc. Current Owner 4/1/2014
U0034938 Fill and Fly, Inc. Former Owner 1/18/2008
U0031999 Convenience & Petroleum Marketing, LLC, Former Owner 8/8/2006
U0008697 Kwik Shop, Inc. Former Owner 10/17/1988
U0022393 The Southland Corporation Former Owner 12/31/1967

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020241962 (Referred to Legal)    Issue Date: 7/11/2024    Expiration Date: 9/9/2024    View NOV Form

Tanks Violations
2 Tank monitor does not appear to function properly and requires maintenance. - CSLD INCR RATE WARNING

NOV Number: E0020242784 (Referred to Legal)    Issue Date: 10/15/2024    Expiration Date: 12/14/2024    View NOV Form

Tanks Violations
1, 3 Failed to Empty the Tank to 1" or Less - Tank#1 & Tank #3 are out service shall be pumped down to one inch or less of product. Tank#1 product level 8.7 inches per ATG. Tank #3 product level 26.31 inches per ATG. Out of Service since 10/10/2024
Facility Miscellaneous - Tank#2 is currently out of service and shall be pumped down to one inch or less of product. Product level is currently at 8.8 inches per ATG.
1, 3 Submit Notification Form For Tank Status Change - Submit Notification Form for Tank Status Change at: https://webapps.sfm.illinois.gov/USTPortal/NotificationForm.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Out of service CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/17/1988 Abandoned Material:
Current Age: 43 Abandoned Date:
Install Date: 6/1/1982 Red Tag Issue Date: 12/18/2024
Last Used Date: 10/15/2024 Fee Due: $0.00
Product Date: 6/1/1982

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Isolation Boots Flex Connector N/A N/A
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 2/27/2024 2/27/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 2/27/2024 2/27/2025
Overfill Prev Device Overfill Alarm 10/5/2022 10/5/2025
Overfill Prev Device Overfill Drop Tube Valve 7/1/2022 7/1/2025
Piping Fiberglass Single Wall Piping Ameron N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Spill Contain Device Single Wall Spill Bucket 6/29/2022 6/29/2025
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Ameron Precision Test (Piping) Pass 2/27/2024
Tank Fiberglass Single Wall Precision Test (Tank) Pass 2/27/2024



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline - Mid-grade CERCLA Substance:
Status: Out of service CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/17/1988 Abandoned Material:
Current Age: 43 Abandoned Date:
Install Date: 6/1/1982 Red Tag Issue Date: 12/18/2024
Last Used Date: 10/10/2024 Fee Due: $0.00
Product Date: 6/1/1982

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Isolation Boots Flex Connector N/A N/A
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 2/27/2024 2/27/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 2/27/2024 2/27/2025
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Alarm 10/5/2022 10/5/2025
Piping Fiberglass Single Wall Piping Ameron N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Spill Contain Device Single Wall Spill Bucket 6/29/2022 6/29/2025
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Ameron Precision Test (Piping) Pass 2/27/2024
Tank Fiberglass Single Wall Precision Test (Tank) Pass 2/27/2024



Tank Number 3

Capacity: 10000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Out of service CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/17/1988 Abandoned Material:
Current Age: 43 Abandoned Date:
Install Date: 6/1/1982 Red Tag Issue Date: 12/18/2024
Last Used Date: 10/15/2024 Fee Due: $0.00
Product Date: 6/1/1982

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Isolation Boots Flex Connector N/A N/A
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 2/27/2024 2/27/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 2/27/2024 2/27/2025
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Alarm 10/5/2022 10/5/2025
Piping Fiberglass Single Wall Piping Ameron N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Spill Contain Device Single Wall Spill Bucket 6/29/2022 6/29/2025
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Ameron Precision Test (Piping) Pass 2/27/2024
Tank Fiberglass Single Wall Precision Test (Tank) Pass 2/27/2024

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found