Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 3007212
Status: Inactive
Facility Name: Delavan Mart, LLC
Address: 201 E. 4th Street Delavan, IL 61734
County: Tazewell
Property Parcel: 21-21-10-119-002
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: U005286
Green Tag Issue Date: 8/19/2019
Green Tag Expiration Date: 12/31/2021

Owner Details

Owner Name: Navpreet Singh
Owner Address: 201 E. 4th Street Delavan, IL 61734
Owner Status: Current Owner
Purchase Date: 4/26/2023
Type of Financial Responsibility: Certificate of Deposit
Financial Responsibility Reporting Due Date: 12/10/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 2/4/2019 12/31/2021

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0041359 Singh, Navpreet Current Owner 4/26/2023
U0041273 Delavan Mart, LLC Former Owner 4/26/2023
U0039452 Star & Star Retail, Inc. Former Owner 12/11/2018
U0037692 Bhalla Oil Company Former Owner 3/4/2015
U0015560 Uselton Oil Company, Inc. Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020251705 (Pending)    Issue Date: 7/8/2025    Expiration Date: 9/6/2025    View NOV Form

Tanks Violations
1, 2, 3, 4, 5 Failed to Empty the Tank to 1" or Less - Per 175.810(a)(1), when placing tanks out of service, the tank and lines must be emptied immediately. The UST is considered empty when all materials have been removed to one inch or less. Upon my reinspection dated 6/16/25, I took stick readings of each tank and all five tanks had more than an inch of product. Tanks were red tagged this date.
1, 2, 3, 4, 5 Remove tank(s) - Single-Walled, Over 30 Years Old and OOS Over One Year - Single walled tanks were taken out of service on 1/13/21, and are greater than 30 years old. Per 175.810(e) tanks must be removed as they are now condemned. Here is a link to the licensed UST Decommissioning contractors, that can perform UST tank removals: https://webapps.sfm.illinois.gov/ustsearch/ContractorSearch.aspx
1, 2, 3, 4, 5 Submit Notification Form For Tank Status Change - Per 175.810(a)(3), tanks taken out of service are required to notify the OSFM within 30 days of date of last use, on an electronic Notification for Underground Storage Tank form, declaring a tank status change. These five tanks were last used on 1/13/21. Here is the link to the electronic Notification for Underground Storage Tank form, so that you can file that change: https://webapps.sfm.illinois.gov/USTPortal/NotificationForm

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
90-3162 Eligible 8/2/1995 9/6/1995 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 8000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Condemned Tank CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/28/1986 Abandoned Material:
Current Age: 49 Abandoned Date:
Install Date: 4/28/1976 Red Tag Issue Date: 6/16/2025
Last Used Date: 1/13/2021 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 5/10/2019 5/10/2020
Corrosion Prot - Piping Isolation Boots Flex Connector N/A N/A
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Impressed Current Cathodic Protection 5/10/2019 5/10/2020
Leak Detect - Piping Electronic Pressurized Line Leak Detection 5/10/2019 5/10/2020
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 5/10/2019 5/10/2020
Overfill Prev Device Overfill Alarm 8/2/2019 8/2/2022
Piping Fiberglass Single Wall Piping N/A N/A
Piping Galvanized Steel Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Spill Contain Device Single Wall Spill Bucket 5/10/2019 5/10/2022
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 3000 Petroleum Use: None
Product: Kerosene CERCLA Substance:
Status: Condemned Tank CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/28/1986 Abandoned Material:
Current Age: 54 Abandoned Date:
Install Date: 4/28/1971 Red Tag Issue Date: 6/16/2025
Last Used Date: 8/19/2019 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 5/10/2019 5/10/2020
Corrosion Prot - Piping Isolation Boots Flex Connector N/A N/A
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Impressed Current Cathodic Protection 5/10/2019 5/10/2020
Leak Detect - Piping European with No Test Req Suction N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 5/10/2019 5/10/2020
Overfill Prev Device Overfill Alarm 8/2/2019 8/2/2022
Piping Fiberglass Single Wall Piping N/A N/A
Piping Galvanized Steel Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Spill Contain Device Single Wall Spill Bucket 5/10/2019 5/10/2022
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 2000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Condemned Tank CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/28/1986 Abandoned Material:
Current Age: 49 Abandoned Date:
Install Date: 4/28/1976 Red Tag Issue Date: 6/16/2025
Last Used Date: 1/13/2021 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 5/10/2019 5/10/2020
Corrosion Prot - Piping Isolation Boots Flex Connector N/A N/A
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Impressed Current Cathodic Protection 5/10/2019 5/10/2020
Leak Detect - Piping Electronic Pressurized Line Leak Detection 5/10/2019 5/10/2020
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 5/10/2019 5/10/2020
Overfill Prev Device Overfill Alarm 8/2/2019 8/2/2022
Piping Fiberglass Single Wall Piping N/A N/A
Piping Galvanized Steel Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Spill Contain Device Single Wall Spill Bucket 5/10/2019 5/10/2022
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 8000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Condemned Tank CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/3/1988 Abandoned Material:
Current Age: 36 Abandoned Date:
Install Date: 10/5/1988 Red Tag Issue Date: 6/16/2025
Last Used Date: 1/13/2021 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 5/10/2019 5/10/2020
Corrosion Prot - Piping Isolation Boots Flex Connector N/A N/A
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Impressed Current Cathodic Protection 5/10/2019 5/10/2020
Leak Detect - Piping Electronic Pressurized Line Leak Detection 7/10/2019 7/10/2020
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 5/10/2019 5/10/2020
Overfill Prev Device Overfill Alarm 8/2/2019 8/2/2022
Piping Fiberglass Single Wall Piping N/A N/A
Piping Galvanized Steel Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Spill Contain Device Single Wall Spill Bucket 5/10/2019 5/10/2022
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 8000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Condemned Tank CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/3/1988 Abandoned Material:
Current Age: 36 Abandoned Date:
Install Date: 10/5/1988 Red Tag Issue Date: 6/16/2025
Last Used Date: 1/13/2021 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 5/10/2019 5/10/2020
Corrosion Prot - Piping Isolation Boots Flex Connector N/A N/A
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Impressed Current Cathodic Protection 5/10/2019 5/10/2020
Leak Detect - Piping Electronic Pressurized Line Leak Detection 5/10/2019 5/10/2020
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 5/10/2019 5/10/2020
Overfill Prev Device Overfill Alarm 8/2/2019 8/2/2022
Piping Fiberglass Single Wall Piping N/A N/A
Piping Galvanized Steel Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Spill Contain Device Single Wall Spill Bucket 5/10/2019 5/10/2022
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A



Name\ID 9

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found