Attendant does not have means to remotely monitor or no emergency shutoff switch 20' to 50' from dispenser - Section 175.210g; All dispensing units shall be readily visible from the control station without assistive devices. If view is permanently obstructed, or the dispenser is located so that activity is not readily visible, closed-circuit cameras that provide a view of each side of the dispensing unit and project an image on a screen at least 6 inches in diagonal located at the control station may be used. You may also elect to install an emergency stop switch at least 20 feet but no more than 50 feet from any dispenser with a permanently obstructed view. SPECIFICALLY DISPENSER 1, 3, 10, 11 AND 12, CANNOT BE VIEWED ON EXISTING CAMERA AND OR IS BLURRED OUT. |