Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2047018
Status: Active
Facility Name: Lenny's Food N Fuel 183rd Street, LLC
Address: 7451 183rd Street Tinley Park, IL 60487
County: Cook
Property Parcel: 09-01-201-016-0000
Facility Type: Commercial / Retail
Owner Type: Private
Green Tag Decal: Z001276
Green Tag Issue Date: 4/11/2024
Green Tag Expiration Date: 12/31/2026

Owner Details

Owner Name: Lenny's Food N Fuel 183rd Street, LLC
Owner Address: 8200 185th Street, Suite K Tinley Park, IL 60487
Owner Status: Current Owner
Purchase Date: 5/26/2020
Type of Financial Responsibility: Designated Savings Account
Financial Responsibility Reporting Due Date: 8/7/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 4/11/2024 12/31/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0041033 Lenny's Food N Fuel 183rd Street, LLC Current Owner 5/26/2020
U0039801 Lenny's Lemont Real Estate Development, LLC Former Owner 2/10/2020

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

No Notice of Violations Found

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/8/2020 Abandoned Material:
Current Age: 5 Abandoned Date:
Install Date: 8/7/2020 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 9/11/2024 9/11/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 9/11/2024 9/11/2025
Overfill Prev Device Overfill Drop Tube Valve 9/20/2023 9/20/2026
Overfill Prev Device Overfill Drop Tube Valve 9/20/2023 9/20/2026
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 9/5/2023 9/5/2026
Leak Detect - Piping Sump Sensor with positive shutdown 9/11/2024 9/11/2025
Spill Contain Device Double Wall Spill Bucket 9/20/2023 9/20/2026
Spill Contain Device Double Wall Spill Bucket 9/20/2023 9/20/2026
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 12/11/2020
Tank Fiberglass Double Wall Containment Solutions Precision Test (Tank) Pass 12/11/2020



Tank Number 2

Capacity: 6000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/8/2020 Abandoned Material:
Current Age: 5 Abandoned Date:
Install Date: 8/7/2020 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 9/11/2024 9/11/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 9/11/2024 9/11/2025
Overfill Prev Device Overfill Drop Tube Valve 9/20/2023 9/20/2026
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 9/5/2023 9/5/2026
Leak Detect - Piping Sump Sensor with positive shutdown 9/11/2024 9/11/2025
Spill Contain Device Double Wall Spill Bucket 9/20/2023 9/20/2026
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 5/1/2025
Tank Fiberglass Double Wall Containment Solutions Precision Test (Tank) Pass 12/11/2020



Tank Number 3

Capacity: 12000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/8/2020 Abandoned Material:
Current Age: 5 Abandoned Date:
Install Date: 8/7/2020 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 9/11/2024 9/11/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 9/11/2024 9/11/2025
Overfill Prev Device Overfill Drop Tube Valve 9/20/2023 9/20/2026
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 9/5/2023 9/5/2026
Leak Detect - Piping Sump Sensor with positive shutdown 9/11/2024 9/11/2025
Spill Contain Device Double Wall Spill Bucket 4/10/2024 4/10/2027
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 12/11/2020
Tank Fiberglass Double Wall Containment Solutions Precision Test (Tank) Pass 12/11/2020



Tank Number 4

Capacity: 10000 Petroleum Use:
Product: E85 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/8/2020 Abandoned Material:
Current Age: 5 Abandoned Date:
Install Date: 8/7/2020 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 9/11/2024 9/11/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 9/11/2024 9/11/2025
Overfill Prev Device Overfill Drop Tube Valve 9/20/2023 9/20/2026
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 9/5/2023 9/5/2026
Leak Detect - Piping Sump Sensor with positive shutdown 9/11/2024 9/11/2025
Spill Contain Device Double Wall Spill Bucket 9/20/2023 9/20/2026
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 12/11/2020
Tank Fiberglass Double Wall Containment Solutions Precision Test (Tank) Pass 12/11/2020



Tank Number 5

Capacity: 3000 Petroleum Use:
Product: Diesel Exhaust Fluid (Non-Regulated) CERCLA Substance:
Status: Unknown CAS Code:
Regulated Status: Non-Regulated Removed Date:
OSFM First Notify Date: 10/8/2020 Abandoned Material:
Current Age: 5 Abandoned Date:
Install Date: 8/7/2020 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/5/2023 9/5/2026
Leak Detect - Piping Sump Sensor with positive shutdown 9/11/2024 9/11/2025



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/5/2023 9/5/2026
Leak Detect - Piping Sump Sensor with positive shutdown 9/11/2024 9/11/2025



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/5/2023 9/5/2026
Leak Detect - Piping Sump Sensor with positive shutdown 9/11/2024 9/11/2025



Name\ID 15/16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/5/2023 9/5/2026
Leak Detect - Piping Sump Sensor with positive shutdown 9/11/2024 9/11/2025



Name\ID 17/18

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/5/2023 9/5/2026
Leak Detect - Piping Sump Sensor with positive shutdown 9/11/2024 9/11/2025



Name\ID 19/20

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/5/2023 9/5/2026
Leak Detect - Piping Sump Sensor with positive shutdown 9/11/2024 9/11/2025



Name\ID 21/22

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/5/2023 9/5/2026
Leak Detect - Piping Sump Sensor with positive shutdown 9/11/2024 9/11/2025



Name\ID 23

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/5/2023 9/5/2026
Leak Detect - Piping Sump Sensor with positive shutdown 9/11/2024 9/11/2025



Name\ID 23/24

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/5/2023 9/5/2026
Leak Detect - Piping Sump Sensor with positive shutdown 9/11/2024 9/11/2025



Name\ID 24/25

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/5/2023 9/5/2026
Leak Detect - Piping Sump Sensor with positive shutdown 9/11/2024 9/11/2025



Name\ID 26

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/5/2023 9/5/2026
Leak Detect - Piping Sump Sensor with positive shutdown 9/11/2024 9/11/2025



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/5/2023 9/5/2026
Leak Detect - Piping Sump Sensor with positive shutdown 9/11/2024 9/11/2025



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/5/2023 9/5/2026
Leak Detect - Piping Sump Sensor with positive shutdown 9/11/2024 9/11/2025



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/5/2023 9/5/2026
Leak Detect - Piping Sump Sensor with positive shutdown 9/11/2024 9/11/2025



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/5/2023 9/5/2026
Leak Detect - Piping Sump Sensor with positive shutdown 9/11/2024 9/11/2025

MFD Motorfuel Dispensing Forms

Facility Number Name City Received Date Letter
2047018 Lenny's Food N Fuel 183rd Street, LLC Tinley Park 10/13/2020 Letter Form
2047018 Lenny's Food N Fuel 183rd Street, LLC Tinley Park 03/13/2020 Letter Form