Line interstitial sensor functional test not accomplished (Required annually). - Blending sump shed sensor annual test needs to be performed. Passing results shall be entered on OSFM portal. |
| Facility |
Miscellaneous - Emergency shut off switch at control station requires a sign.
175.210 d) 3) Equipped with an emergency stop at all control stations, which shall be
conspicuously marked and readily accessible to the attendant, whether or
not the control station is less than 20 feet from any dispenser or a security
booth is provided for the attendant. The emergency stop shall be located
in a position to allow all dispensing devices to be readily visible to the
attendant, or as approved by OSFM. Each emergency stop shall be
identified by a sign on all-weather materials stating "EMERGENCY
STOP" in 2 inch red capital letters. |
| Facility |
Missing copies of current testing certificates for operator training |
| Facility |
Missing list of designated Class A/B & C Operators |
| 1, 2, 3, 4 |
Monthly line interstitial sensor records not available. - 2 years of monthly line interstitial records are required to be kept on site. |
| 1, 2, 3, 4 |
Precision line test required. - 2 years of monthly line interstitial records are not available a precision line test is required. |
| 1, 2, 3, 4 |
Precision tank test required. - 2 years of monthly tank interstitial records are not available a precision tank test is required. |
| 1, 2, 3, 4 |
Required monthly tank interstitial sensor records not available. - 2 years of monthly tank interstitial records are required to be kept on site. |