Facility Details

Facility Number: 2046456
Status: Active
Facility Name: Pilot Travel Center
Address: 1050 Busse Road Bensenville, IL 60106
County: Du Page
Property Parcel: 03-03-208-015
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y002801
Green Tag Issue Date: 1/24/2024
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Pilot Travel Centers, LLC
Owner Address: 5508 Lonas Rd. Knoxville, TN 37909
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 8/18/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 1/27/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0011913 Pilot Travel Centers, LLC Current Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020252226 (Pending)    Issue Date: 8/27/2025    Expiration Date: 10/26/2025    View NOV Form

Tanks Violations
4 Miscellaneous - We received a report showing a failed precision piping test.
1, 2, 3, 4 Overfill prevention equipment inspection(s) not completed (Required every 3 years). - Over fill alarm needs triannual testing. Section 175.405 Spill Containment and Overfill Prevention Equipment c) Overfill prevention equipment must be inspected at installation, immediately after any repairs, and at least once every three years, and the inspection shall meet the following criteria: 1) At a minimum, the inspection must ensure that overfill prevention equipment is set to activate at the correct level specified in subsection (a); 2) The overfill prevention equipment will activate when the regulated substance reaches that level; and 3) Inspections must be conducted in accordance with inspection requirements developed by the manufacturer.

NOV Number: E0020252671 (Pending)    Issue Date: 10/8/2025    Expiration Date: 12/7/2025    View NOV Form

Tanks Violations
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - 175.210 h)The attendant shall at all times be able to communicate with persons in the dispensing area. Repair or replace intercom.

NOV Number: E0020252672 (Pending)    Issue Date: 10/8/2025    Expiration Date: 12/7/2025    View NOV Form

Tanks Violations
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - Emergency shut off switch needs annual testing performed. OSFM form shall be kept on site.
1, 2, 3, 4 Document that emergency shut-off (shear valves) are in proper working order - Shear valves need annual testing performed. OSFM form shall be completed and kept on site.
3, 4 Line interstitial sensors have been raised and rendered inoperational. - T4 Shed blending sump and dispenser 20. Section 175.640 a)2) All new and existing sump sensors must be installed so as to detect liquid per manufacturer's specifications or, if not specified by the manufacturer, at the lowest point in the sump.
Facility Miscellaneous - Emergency shut off sign needs to be replaced. It's difficult to read. Truck side west sign. 175.210 d) 3) Equipped with an emergency stop at all control stations, which shall be conspicuously marked and readily accessible to the attendant, whether or not the control station is less than 20 feet from any dispenser or a security booth is provided for the attendant. The emergency stop shall be located in a position to allow all dispensing devices to be readily visible to the attendant, or as approved by OSFM. Each emergency stop shall be identified by a sign on all-weather materials stating "EMERGENCY STOP" in 2 inch red capital letters.
3, 4 Miscellaneous - There is product in shed blending sump and dispenser 20 UDC sump.
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30 day walkthrough are not on site for review.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual walkthrough needs to be performed. OSFM form shall be completed and kept on site.
1, 2, 3, 4 Monthly line interstitial sensor records not available.
1, 2, 3, 4 Piping interstitial must be open in all sumps - 175.420 b) Unless otherwise required by the manufacturer, the dispenser product piping sump jumper tubes shall be removed, or the product piping test boots pulled back after testing to allow the interstice to be open to the sump sensors. This is for all sumps.
1, 2, 3, 4 Precision line test required. - Since two years of piping sensors are not on site a precision tank test is required.
1, 2, 3, 4 Precision tank test required. - Since two years of tank sensors are not on site a precision tank test is required.
1, 2, 3, 4 Required monthly tank interstitial sensor records not available. - 2 years of monthly tank interstitial records are required to be kept on site.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 16000 Gasoline - Regular Currently in use Federal $0.00
2 9000 Gasoline - Premium Currently in use Federal $0.00
3 30000 Diesel Fuel Currently in use Federal $0.00
4 20000 B-99 Currently in use Federal $0.00
5 12000 Diesel Exhaust Fluid (Non-Regulated) Unknown Non-Regulated $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active
9/10 Active
11/12 Active
17 m Active
17 sat Active
18 Active
19 Active
20 Active
21 Active
22 Active

MFD Motorfuel Dispensing Forms

Facility Number Name City Received Date Letter
2046456 Pilot Travel Center Bensenville 08/21/2017 Letter Form