Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2046275
Status: Active
Facility Name: Grove Stop
Address: 11 Waubonsee Dr. Sugar Grove, IL 60554
County: Kane
Property Parcel: 14-08-251-032
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: AA03953
Green Tag Issue Date: 1/8/2026
Green Tag Expiration Date: 12/31/2027

Owner Details

Owner Name: Elferno, LLC Series B
Owner Address: 725 S. Euclid Ave. Elmhurst, IL 60126
Owner Status: Current Owner
Purchase Date: 10/1/2016
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 4/7/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 1/8/2026 12/31/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0039124 Elferno, LLC Series B Current Owner 10/1/2016
U0038518 Raafat Zaiter Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020260059 (Pending)    Issue Date: 1/8/2026    Expiration Date: 3/9/2026    View NOV Form

Tanks Violations
1, 2, 3 Annual electronic line leak detector test not completed. - Line leak detectors need annual testing. Testing shall be performed and passing results entered on OSFM portal.
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - Emergency shut off switch needs annual testing performed. OSFM form shall be kept on site.
1, 2, 3 Annual leak detection certification not completed (Required annually). - Annual leak detection testing shall be performed and passing results entered on OSFM portal.
1, 2, 3 Document that emergency shut-off (shear valves) are in proper working order - Shear valves need annual testing performed. OSFM form shall be completed and kept on site.
1, 2, 3 Line interstitial sensor functional test not accomplished (Required annually). - STP and UDC sump sensors STP and UDC sump sensors need annual testing performed. Passing results shall be entered on OSFM portal.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual walkthrough needs to be performed. OSFM form shall be completed and kept on site.
1, 2, 3 Tank interstitial sensor functional test not accomplished (Required annually). - Tank sensor needs annual testing perfomed. Passing results shall be entered on OSFM portal.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/5/2018 Abandoned Material:
Current Age: 9 Abandoned Date:
Install Date: 10/27/2016 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 1/9/2026 1/9/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 1/9/2026 1/9/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 1/9/2026 1/9/2027
Overfill Prev Device Overfill Drop Tube Valve 4/3/2025 4/3/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 4/3/2025 4/3/2028
Leak Detect - Piping Sump Sensor with positive shutdown 1/9/2026 1/9/2027
Spill Contain Device Double Wall Spill Bucket 4/3/2025 4/3/2028
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/5/2018 Abandoned Material:
Current Age: 9 Abandoned Date:
Install Date: 10/27/2016 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 1/9/2026 1/9/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 1/9/2026 1/9/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 1/9/2026 1/9/2027
Overfill Prev Device Overfill Drop Tube Valve 4/3/2025 4/3/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 4/3/2025 4/3/2028
Leak Detect - Piping Sump Sensor with positive shutdown 1/9/2026 1/9/2027
Spill Contain Device Double Wall Spill Bucket 4/3/2025 4/3/2028
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 12000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/5/2018 Abandoned Material:
Current Age: 9 Abandoned Date:
Install Date: 10/27/2016 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 1/9/2026 1/9/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 1/9/2026 1/9/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 1/9/2026 1/9/2027
Overfill Prev Device Overfill Drop Tube Valve 4/3/2025 4/3/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 4/3/2025 4/3/2028
Leak Detect - Piping Sump Sensor with positive shutdown 1/9/2026 1/9/2027
Spill Contain Device Double Wall Spill Bucket 4/3/2025 4/3/2028
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/3/2025 4/3/2028
Leak Detect - Piping Sump Sensor with positive shutdown 1/9/2026 1/9/2027



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/3/2025 4/3/2028
Leak Detect - Piping Sump Sensor with positive shutdown 1/9/2026 1/9/2027



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/3/2025 4/3/2028
Leak Detect - Piping Sump Sensor with positive shutdown 1/9/2026 1/9/2027



Name\ID 14S/15

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/3/2025 4/3/2028
Leak Detect - Piping Sump Sensor with positive shutdown 1/9/2026 1/9/2027



Name\ID 15S

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/3/2025 4/3/2028
Leak Detect - Piping Sump Sensor 1/9/2026 1/9/2027



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/3/2025 4/3/2028
Leak Detect - Piping Sump Sensor with positive shutdown 1/9/2026 1/9/2027



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/3/2025 4/3/2028
Leak Detect - Piping Sump Sensor with positive shutdown 1/9/2026 1/9/2027



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/3/2025 4/3/2028
Leak Detect - Piping Sump Sensor with positive shutdown 1/9/2026 1/9/2027



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/3/2025 4/3/2028
Leak Detect - Piping Sump Sensor with positive shutdown 1/9/2026 1/9/2027

MFD Motorfuel Dispensing Forms