Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2045956
Status: Active
Facility Name: Ozinga Bros, Inc.
Address: 10101 IL Route 31 Algonquin, IL 60102
County: McHenry
Property Parcel: 19-22-251-004
Facility Type: Industrial / Manufacturing
Owner Type: Private
Green Tag Decal: Z003998
Green Tag Issue Date: 4/29/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Fleet

Owner Details

Owner Name: Meyer Material Company
Owner Address: 1300 S. IL Route 31 South Elgin, IL 60050
Owner Status: Current Owner
Purchase Date: 12/15/1997
Type of Financial Responsibility: Certificate of Deposit
Financial Responsibility Reporting Due Date: 4/2/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0010204 Meyer Material Company Current Owner 12/15/1997

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
00281-2026UPG Upgrade Approved / Issued 3/13/2026 3/14/2026 9/15/2026 Documents

Notice of Violatlions (Current)

NOV Number: E0020260457 (Pending)    Issue Date: 2/24/2026    Expiration Date: 4/25/2026    View NOV Form

Tanks Violations
Facility Fire Extinguishers - Minimum 4A:60BC are not present at each island and at an emergency shutoff switch - PROVIDE 2 FIRE EXTINGUISHERS PER ABOVE AND HAVE THEM CLEARLY MARKED AND ACCESSIBLE.
Facility Fire Extinguishers - Past due for annual testing - Fire extinguishers require annual testing. Have annual testing performed and tag all fire extinguishers accordingly.

NOV Number: E0020260458 (Pending)    Issue Date: 2/24/2026    Expiration Date: 4/25/2026    View NOV Form

Tanks Violations
Facility Emergency contact information for A/B & C Operators not posted at unmanned facility - CURRENT EMERGENCY RESPONSE PROCEDURES POSTED AT FACILITY, AS THE CONTACT INFO, DOES NOT SHOW CURRENT AB OPERATOR CONTACT INFO. MUST UPDATE.
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30-day Walkthrough Inspection shall be completed, and 2 years of documentation maintained on site. 30-Day Walkthrough Inspection form available at www.sfm.illinois.gov. The form must be filled out by an A/B Operator, you must, initial each box that applies, date the form each month to ensure it is being done every 30 days, and the A/B operator must print and sign their name at the bottom. If more than one A/B operator fills out the form, then each must print and sign name at the bottom. Missing 6/2025 to present.
Facility Missing copy of emergency instructions or emergency procedures plan - CURRENT EMERGENCY RESPONSE PROCEDURES DOES NOT SHOW CURRENT AB OPERATOR CONTACT INFO. MUST UPDATE.
Facility Missing list of designated Class A/B & C Operators - UPDATE LIST
1 Monthly line interstitial sensor records not available. - Maintain one NORMAL report per LINE, per month, from ATG. Must maintain 24 months’ worth. Missing 4/2025 to present.
1 Overfill prevention equipment inspection(s) not completed (Required every 3 years). - Triennial inspection of overfill device (overfill alarm) has not been completed. Testing shall be completed with passing results and uploaded to OSFM website.
1 Required monthly tank interstitial sensor records not available. - Maintain one NORMAL report per TANK, per month, from ATG. Must maintain 24 months’ worth. Missing 4/2025 to present.
1 Tank monitor does not appear to function properly and requires maintenance. - Green Indicator light on panel of Veeder-Root ATG is not functional. Replace as necessary to provide proper operation.
1 Tank precision test required. - Precision tank test is required on tank(s) if you cannot provide 24 months’ worth of tank “NORMAL” from ATG. Missing 4/2025 to present.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 10000 Diesel Fuel Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1 Active

MFD Motorfuel Dispensing Forms

No Forms Found