Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2045858
Status: Active
Facility Name: SAIA LTL Freight
Address: 2260 S Midlothian Rd Grayslake, IL 60030
County: Lake
Property Parcel: 10-12-300-037
Facility Type: Trucking Company
Owner Type: Private
Green Tag Decal: Z003568
Green Tag Issue Date: 7/11/2024
Green Tag Expiration Date: 12/31/2026

Owner Details

Owner Name: Saia Motor Freight Lines, LLC
Owner Address: 11465 Johns Creek Pkwy Suite 330 Johns Creek, GA 30097
Owner Status: Current Owner
Purchase Date: 7/1/2015
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 10/4/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Fleet 7/11/2024 12/31/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0035172 Saia Motor Freight Lines, LLC Current Owner 7/1/2015

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020252130 (Pending)    Issue Date: 8/19/2025    Expiration Date: 10/18/2025    View NOV Form

Tanks Violations
1, 2 Annual leak detection certification not completed (Required annually). - ATG testing Failed. ATG fails due to both tank probes not reading anything at departure. Once probe cables were disconnected from probes, they never reconnected.
Facility Financial responsibility must be reported yearly - Financial Responsibility shall be declared annually; declaration form can be found at https://webapps.sfm.illinois.gov/USTPortal/forms/FinancialResponsibility. Complete form online and submit electronically.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 20000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/5/2016 Abandoned Material:
Current Age: 9 Abandoned Date:
Install Date: 8/28/2015 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 3/14/2016

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Siphon Bar N/A N/A
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 6/25/2024 5/22/2025
Overfill Prev Device Overfill Alarm 5/22/2025 5/22/2028
Overfill Prev Device Overfill Drop Tube Valve 5/22/2025 5/22/2028
Piping Fiberglass Double Wall A.O. Smith N/A N/A
Piping Single Wall STP/Tanktop Sump 4/15/2024 4/15/2027
Leak Detect - Piping Sump Sensor with positive shutdown 5/22/2025 5/22/2026
Spill Contain Device Single Wall Spill Bucket 5/22/2025 5/22/2028
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall A.O. Smith Precision Test (Piping) Pass 5/22/2025
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 4/15/2024



Tank Number 2

Capacity: 20000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/5/2016 Abandoned Material:
Current Age: 9 Abandoned Date:
Install Date: 8/28/2015 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 3/14/2016

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 5/22/2025 5/22/2026
Leak Detect - Piping Siphon Bar N/A N/A
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 6/25/2024 5/22/2025
Overfill Prev Device Overfill Alarm 5/22/2025 5/22/2028
Overfill Prev Device Overfill Drop Tube Valve 5/22/2025 5/22/2028
Piping Fiberglass Double Wall A.O. Smith N/A N/A
Piping Single Wall STP/Tanktop Sump 4/15/2024 4/15/2027
Leak Detect - Piping Sump Sensor with positive shutdown 5/22/2025 5/22/2026
Spill Contain Device Single Wall Spill Bucket 5/22/2025 5/22/2028
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall A.O. Smith Precision Test (Piping) Pass 4/15/2024
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 4/15/2024



Tank Number 3

Capacity: 8000 Petroleum Use: None
Product: Diesel Exhaust Fluid (Non-Regulated) CERCLA Substance:
Status: Unknown CAS Code:
Regulated Status: Non-Regulated Removed Date:
OSFM First Notify Date: 4/5/2016 Abandoned Material:
Current Age: 9 Abandoned Date:
Install Date: 8/28/2015 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 3/14/2016

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection
Leak Detect - Piping Sump Sensor
Leak Detect - Tank Automatic Tank Gauging OPW Site Sentinel Integra 100
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors
Overfill Prev Device Overfill Drop Tube Valve
Piping Fiberglass Double Wall A.O. Smith N/A N/A
Spill Contain Device Single Wall Spill Bucket 4/15/2024 4/15/2027
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/4/2018 9/4/2021
Leak Detect - Piping Sump Sensor 5/22/2025 5/22/2026



Name\ID 1 Sat

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/30/2021 8/30/2024
Leak Detect - Piping Sump Sensor with positive shutdown 4/9/2021 4/9/2022



Name\ID 1/2 Main

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/30/2021 8/30/2024
Leak Detect - Piping Sump Sensor with positive shutdown 4/9/2021 4/9/2022



Name\ID 2 Sat

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/15/2024 4/15/2027
Leak Detect - Piping Sump Sensor with positive shutdown 6/25/2024 6/25/2025



Name\ID 2 sat

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/30/2021 8/30/2024
Leak Detect - Piping Sump Sensor 5/22/2025 5/22/2026



Name\ID 2/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 5/24/2024 5/24/2027
Leak Detect - Piping Sump Sensor 5/22/2025 5/22/2026



Name\ID 3

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/4/2018 9/4/2021
Leak Detect - Piping Sump Sensor 5/22/2025 5/22/2026



Name\ID 4 Sat

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/15/2024 4/15/2027
Leak Detect - Piping Sump Sensor 5/22/2025 5/22/2026

MFD Motorfuel Dispensing Forms

No Forms Found