Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2045665
Status: Active
Facility Name: DL Food Mart, Inc.
Address: 1600 W. Lake St. Roselle, IL 60172
County: Du Page
Property Parcel: 02-08-217-005
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y002775
Green Tag Issue Date: 6/16/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Riteline Development, LLC
Owner Address: 300 N. Martingale Rd. Schaumburg, IL 60173
Owner Status: Current Owner
Purchase Date: 7/1/2014
Type of Financial Responsibility: Designated Savings Account
Financial Responsibility Reporting Due Date: 8/4/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 6/16/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0037853 Riteline Development, LLC Current Owner 7/1/2014
U0035798 Stambolic, R E, LLC Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020252883 (Pending)    Issue Date: 10/29/2025    Expiration Date: 12/28/2025    View NOV Form

Tanks Violations
1, 2 Dispensers - hoses cracked, split or worn and require replacement - Replace main hoses on the following dispensers.
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30 day walkthroughs are required to be performed and documented on OSFM 30 Day Form which can be found at https://sfm.illinois.gov/
1, 2, 3, 4 Monthly line interstitial sensor records not available. - 2 years of monthly line interstitial records are required to be kept on site.
1, 2, 3, 4 Piping interstitial must be open in all sumps - 175.420 b) Unless otherwise required by the manufacturer, the dispenser product piping sump jumper tubes shall be removed, or the product piping test boots pulled back after testing to allow the interstice to be open to the sump sensors. This is for all sumps.
1, 2, 3, 4 Precision line test required. - Since 2 years of monthly line interstitial records are not available a precision line test is required.
1, 2, 3, 4 Precision tank test required. - Since 2 years of monthly tank interstitial records are not available a precision tank test is required.
1, 2, 3, 4 Required monthly tank interstitial sensor records not available. - 2 years of monthly tank interstitial records are required to be kept on site.
1, 2, 3, 4 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - 175.405 a) 1) A) Spill containment equipment that will prevent release of product to the environment when the transfer hose is detached from the fill pipe (e.g., a spill catch basin). Spill containment equipment shall be maintained in a dry, clean state.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 6/26/2015 Abandoned Material:
Current Age: 10 Abandoned Date:
Install Date: 8/14/2014 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 4/1/2015

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 2/24/2025 2/24/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 2/24/2025 2/24/2026
Overfill Prev Device Overfill Drop Tube Valve 4/11/2025 4/11/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 4/11/2025 4/11/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/24/2025 2/24/2026
Leak Detect - Piping Sump Sensor with positive shutdown 4/11/2025 4/11/2026
Spill Contain Device Single Wall Spill Bucket 4/11/2025 4/11/2028
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 9/22/2021
Tank Fiberglass Double Wall Containment Solutions Precision Test (Tank) Pass 9/22/2021



Tank Number 2

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 6/26/2015 Abandoned Material:
Current Age: 10 Abandoned Date:
Install Date: 8/14/2014 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 4/1/2015

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 2/24/2025 2/24/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 2/24/2025 2/24/2026
Overfill Prev Device Overfill Drop Tube Valve 4/11/2025 4/11/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 4/11/2025 4/11/2028
Leak Detect - Piping Non-Discriminating Sump Sensor with positive shutdown 3/24/2021 3/24/2022
Leak Detect - Piping Sump Sensor with positive shutdown 2/24/2025 2/24/2026
Spill Contain Device Single Wall Spill Bucket 4/11/2025 4/11/2028
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 9/22/2021
Tank Fiberglass Double Wall Containment Solutions Precision Test (Tank) Pass 9/22/2021



Tank Number 3

Capacity: 6000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 6/26/2015 Abandoned Material:
Current Age: 10 Abandoned Date:
Install Date: 8/14/2014 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 4/1/2015

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 2/24/2025 2/24/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 2/24/2025 2/24/2026
Overfill Prev Device Overfill Drop Tube Valve 4/11/2025 4/11/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 4/11/2025 4/11/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/24/2025 2/24/2026
Spill Contain Device Single Wall Spill Bucket 4/11/2025 4/11/2028
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 9/22/2021
Tank Fiberglass Double Wall Containment Solutions Precision Test (Tank) Pass 9/22/2021



Tank Number 4

Capacity: 6000 Petroleum Use:
Product: E85 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 6/26/2015 Abandoned Material:
Current Age: 10 Abandoned Date:
Install Date: 8/14/2014 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 4/1/2015

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 2/24/2025 2/24/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 2/24/2025 2/24/2026
Overfill Prev Device Overfill Drop Tube Valve 4/11/2025 4/11/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 4/11/2025 4/11/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/24/2025 2/24/2026
Spill Contain Device Single Wall Spill Bucket 4/11/2025 4/11/2028
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 8/7/2023
Tank Fiberglass Double Wall Containment Solutions Precision Test (Tank) Pass 9/22/2021

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/11/2025 4/11/2028
Leak Detect - Piping Sump Sensor 2/24/2025 2/24/2026



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/11/2025 4/11/2028
Leak Detect - Piping Sump Sensor 2/24/2025 2/24/2026



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/11/2025 4/11/2028
Leak Detect - Piping Sump Sensor 2/24/2025 2/24/2026



Name\ID 15/16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/11/2025 4/11/2028
Leak Detect - Piping Sump Sensor 2/24/2025 2/24/2026



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/11/2025 4/11/2028
Leak Detect - Piping Sump Sensor 2/24/2025 2/24/2026



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/11/2025 4/11/2028
Leak Detect - Piping Sump Sensor 2/24/2025 2/24/2026



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/11/2025 4/11/2028
Leak Detect - Piping Sump Sensor 2/24/2025 2/24/2026



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/11/2025 4/11/2028
Leak Detect - Piping Sump Sensor 2/24/2025 2/24/2026

MFD Motorfuel Dispensing Forms

No Forms Found