Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - T1 regular tank top well covers are broken. Two composite covers for probe and annular sensor are cracked. Replace lid covers. |
| 2, 4 |
Miscellaneous - T2 Premium double wall spill bucket gauge broken. T4 E85 vapor bucket gauge is broken. |
| 1, 2, 3, 4 |
Piping interstitial must be open in all sumps - 175.420 b) Unless otherwise required by the manufacturer, the dispenser product piping sump jumper tubes shall be removed, or the product piping test boots pulled back after testing to allow the interstice to be open to the sump sensors. This is for all sumps. |