Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2044233
Status: Active
Facility Name: Casey's #2827
Address: 602 East Street Mazon, IL 60444
County: Grundy
Property Parcel: 08-15-300-003
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z000185
Green Tag Issue Date: 9/4/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: Casey's Retail Company
Owner Address: 3305 SE Delaware Ave. P.O. Box 3004 Ankeny, IA 50021
Owner Status: Current Owner
Purchase Date: 4/29/2009
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 1/29/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0002560 Casey's Retail Company Current Owner 4/29/2009

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020260426 (Pending)    Issue Date: 2/23/2026    Expiration Date: 4/24/2026    View NOV Form

Tanks Violations
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - 175.210 h)The attendant shall at all times be able to communicate with persons in the dispensing area. Repair or replace intercom.

NOV Number: E0020260428 (Pending)    Issue Date: 2/23/2026    Expiration Date: 4/24/2026    View NOV Form

Tanks Violations
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - Emergency shut off switch needs annual testing performed. OSFM form shall be kept on site.
1, 2, 3 Document that emergency shut-off (shear valves) are in proper working order - Shear valves need annual testing performed. OSFM form shall be completed and kept on site.
Facility Facility Operation and Maintenance Plan not completed or available. - Operations and Maintenance Template needs to be updated and kept on site. https://sfm.illinois.gov/
Facility Missing copies of 30 day Walkthrough Inspection Report. - 1 thru 7/2025 a 30 day walkthrough was not completed or records are not available. 30 day walkthroughs are required to be performed and documented on OSFM 30 Day Form which can be found at https://sfm.illinois.gov/
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30 day walkthroughs are required to be performed and documented on OSFM 30 Day Form which can be found at https://sfm.illinois.gov/
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual walkthrough needs to be performed. OSFM form shall be completed and kept on site.
Facility Missing copies of current testing certificates for operator training - All A/B and C operator certificates shall be kept on site in OSFM binder for review.
Facility Missing copy of emergency instructions or emergency procedures plan - Emergency Procedures Plan needs to be updated and kept on site. https://sfm.illinois.gov/
Facility Missing list of designated Class A/B & C Operators - A list of designated operators is required to be kept on site so OSFM representative can review them. This shall be kept in the OSFM binder.
1, 2, 3 Monthly line interstitial sensor records not available. - Monthly records are not available from 1/2025 through 5/2025. 2 years of monthly tank interstitial records are required to be kept on site.
1, 2, 3 Precision line test required. - 2 years of monthly tank interstitial records are not available a precision tank test is required.
1, 2, 3 Precision tank test required. - 2 years of passing monthly tank tests are not available a precision tank test is required.
1, 2, 3 Required monthly tank leak test records not available. - Monthly records are not available from 1/2025 through 5/2025. 2 years of passing monthly tank tests are required to be kept on site.
1, 2, 3 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - 175.405 a) 1) A) Spill containment equipment that will prevent release of product to the environment when the transfer hose is detached from the fill pipe (e.g., a spill catch basin). Spill containment equipment shall be maintained in a dry, clean state.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 20000 Gasoline - Regular Currently in use Federal $0.00
2 12000 Gasoline - Premium Currently in use Federal $0.00
3 8000 Diesel Fuel Currently in use Federal $0.00

Dispenser Information

Name\ID Status
5/6 Active
7/8 Active
1/2 Active
3/4 Active

MFD Motorfuel Dispensing Forms

No Forms Found