Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2044091
Status: Active
Facility Name: Grand Avenue Station
Address: 3601 W. Grand Avenue Chicago, IL 60651
County: Cook
Property Parcel: 16-02-308-038-0000
Facility Type: Attended Self-Service/Unattended Self-Service
Owner Type: Private
Green Tag Decal: AA02269
Green Tag Issue Date: 5/27/2025
Green Tag Expire Date: 12/31/2027
MFD Type: Self Service

Owner Details

Owner Name: 3601 West Grand, LLC
Owner Address: 26 Mill Plain Road Danbury, CT 06811
Owner Status: Current Owner
Purchase Date: 6/19/2023
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 4/21/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0040944 3601 West Grand, LLC Current Owner 6/19/2023
U0034838 Grand Mobil Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020260551 (Pending)    Issue Date: 3/3/2026    Expiration Date: 5/2/2026    View NOV Form

Tanks Violations
2 Tank interstitial sensors in alarm or failed test, must repair or replace. - Tested by Midwest Tank Tightness, Inc. on 2/18/26 and won't come out of alarm needs replacement.
2, 3 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress.
1, 2, 3 Water in dispenser containment with interstitial sensors - Remove water and repair containments to prevent water ingress

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 2/5/2009 Abandoned Material:
Current Age: 17 Abandoned Date:
Install Date: 7/11/2008 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/7/2009

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 2/18/2026 2/18/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 2/18/2026 2/18/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 2/18/2026 2/18/2027
Overfill Prev Device Overfill Drop Tube Valve 5/23/2025 5/23/2028
Piping Fiberglass Double Wall A.O. Smith N/A N/A
Piping Single Wall STP/Tanktop Sump 2/18/2026 2/18/2029
Leak Detect - Piping Sump Sensor 2/18/2026 2/18/2027
Spill Contain Device Single Wall Spill Bucket 5/13/2025 5/13/2028
Tank Composite Double Wall Modern Welding Glasteel II N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall A.O. Smith Precision Test (Piping) Pass 2/6/2025



Tank Number 2

Capacity: 6000 Petroleum Use:
Product: E85 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 2/5/2009 Abandoned Material:
Current Age: 17 Abandoned Date:
Install Date: 7/11/2008 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/7/2009

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 2/18/2026 2/18/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 2/18/2026 2/18/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 2/6/2025 2/6/2026
Overfill Prev Device Overfill Drop Tube Valve 5/13/2025 5/13/2028
Piping Fiberglass Double Wall A.O. Smith N/A N/A
Piping Single Wall STP/Tanktop Sump 2/18/2026 2/18/2029
Leak Detect - Piping Sump Sensor 2/18/2026 2/18/2027
Spill Contain Device Single Wall Spill Bucket 5/13/2025 5/13/2028
Tank Composite Double Wall Modern Welding Glasteel II N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall A.O. Smith Precision Test (Piping) Pass 2/6/2025



Tank Number 3

Capacity: 4000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 2/5/2009 Abandoned Material:
Current Age: 17 Abandoned Date:
Install Date: 7/11/2008 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/7/2009

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 2/18/2026 2/18/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 2/18/2026 2/18/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 4/6/2026 4/6/2027
Overfill Prev Device Overfill Drop Tube Valve 5/13/2025 5/13/2028
Piping Fiberglass Double Wall A.O. Smith N/A N/A
Piping Single Wall STP/Tanktop Sump 2/18/2026 2/18/2029
Leak Detect - Piping Sump Sensor 2/18/2026 2/18/2027
Spill Contain Device Single Wall Spill Bucket 5/13/2025 5/13/2028
Tank Composite Double Wall Modern Welding Glasteel II N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall A.O. Smith Precision Test (Piping) Pass 2/6/2025

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/18/2026 2/18/2029
Leak Detect - Piping Sump Sensor 2/18/2026 2/18/2027



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/18/2026 2/18/2029
Leak Detect - Piping Sump Sensor 2/18/2026 2/18/2027



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/18/2026 2/18/2029
Leak Detect - Piping Sump Sensor 2/18/2026 2/18/2027



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/18/2026 2/18/2029
Leak Detect - Piping Sump Sensor 2/18/2026 2/18/2027

MFD Motorfuel Dispensing Forms

No Forms Found