Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2043141
Status: Active
Facility Name: Woodman's Gas/Lube & Car Wash
Address: 150 Hansen Boulevard North Aurora, IL 60542
County: Kane
Property Parcel: 15-06-155-019
Facility Type: Attended Self-Service/Unattended Self-Service
Owner Type: Private
Green Tag Decal: Z003427
Green Tag Issue Date: 2/9/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Unattended Self Service

Owner Details

Owner Name: Woodman's Food Market, Inc.
Owner Address: 2631 Liberty Lane Janesville, WI 535450741
Owner Status: Current Owner
Purchase Date: 5/8/2006
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 6/28/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0030284 Woodman's Food Market, Inc. Current Owner 5/8/2006

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020260153 (Pending)    Issue Date: 1/21/2026    Expiration Date: 3/22/2026    View NOV Form

Tanks Violations
3 Piping containment sump failed triennial testing. Repair or replace. - Protanic failed STP sump on 6/30/2025. Repair shall be made and passing testing results entered on OSFM portal.
5 Tank interstitial sensor functional test not accomplished (Required annually). - Annual testing is required for tank 5 interstitial sensor. Passing results shall be entered on OSFM portal.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/23/2006 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: 5/22/2006 Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date: 8/8/2006

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Electronic Pressurized Line Leak Detection 6/29/2026 6/29/2027
Leak Detect - Tank Automatic Tank Gauging Franklin Fueling Systems EVO 600 6/29/2026 6/29/2027
Overfill Prev Device Overfill Alarm 6/30/2025 6/30/2028
Piping Fiberglass Double Wall A.O. Smith Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump 6/30/2025 6/30/2028
Leak Detect - Piping Sump Sensor with positive shutdown 6/30/2025 6/30/2028
Spill Contain Device Single Wall Spill Bucket 6/30/2025 6/30/2028
Tank Fiberglass Single Wall Containment Solutions Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Tank Fiberglass Single Wall Containment Solutions Precision Test (Tank) Pass 1/24/2025



Tank Number 2

Capacity: 6000 Petroleum Use:
Product: E85 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/23/2006 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: 5/22/2006 Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date: 8/8/2006

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Electronic Pressurized Line Leak Detection 6/29/2026 6/29/2027
Leak Detect - Tank Automatic Tank Gauging Franklin Fueling Systems EVO 600 with SCALD 6/29/2026 6/29/2027
Overfill Prev Device Overfill Alarm 6/30/2025 6/30/2028
Piping Fiberglass Double Wall A.O. Smith Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump 6/30/2025 6/30/2028
Leak Detect - Piping Sump Sensor with positive shutdown 6/30/2025 6/30/2028
Spill Contain Device Single Wall Spill Bucket 6/30/2025 6/30/2028
Tank Fiberglass Single Wall Containment Solutions Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall A.O. Smith Precision Test (Piping) Pass 2/13/2024



Tank Number 3

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/23/2006 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: 5/22/2006 Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date: 8/8/2006

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Electronic Pressurized Line Leak Detection 6/29/2026 6/29/2027
Leak Detect - Tank Automatic Tank Gauging Franklin Fueling Systems EVO 600 with SCALD 6/29/2026 6/29/2027
Overfill Prev Device Overfill Alarm 6/30/2025 6/30/2028
Piping Fiberglass Double Wall A.O. Smith Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump 1/11/2023 6/30/2025
Leak Detect - Piping Sump Sensor with positive shutdown 1/11/2023 6/30/2025
Spill Contain Device Single Wall Spill Bucket 6/30/2025 6/30/2028
Tank Fiberglass Single Wall Containment Solutions Not applicable Not applicable

Additional Tests

No Tests Listed




Tank Number 4

Capacity: 6000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/23/2006 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: 5/22/2006 Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date: 8/8/2006

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Electronic Pressurized Line Leak Detection 6/29/2026 6/29/2027
Leak Detect - Tank Automatic Tank Gauging Franklin Fueling Systems EVO 600 with SCALD 6/29/2026 6/29/2027
Overfill Prev Device Overfill Alarm 6/30/2025 6/30/2028
Piping Fiberglass Double Wall A.O. Smith Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump 6/30/2025 6/30/2028
Leak Detect - Piping Sump Sensor with positive shutdown 6/30/2025 6/30/2028
Spill Contain Device Single Wall Spill Bucket 6/30/2025 6/30/2028
Tank Fiberglass Single Wall Containment Solutions Not applicable Not applicable

Additional Tests

No Tests Listed




Tank Number 5

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/10/2012 Abandoned Material:
Current Age: 13 Abandoned Date:
Install Date: 8/2/2012 Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date:

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Electronic Pressurized Line Leak Detection 6/29/2026 6/29/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 6/29/2026 6/29/2027
Overfill Prev Device Overfill Alarm 6/30/2025 6/30/2028
Overfill Prev Device Overfill Drop Tube Valve 6/30/2025 6/30/2028
Piping Flexible Double Wall Franklin Fueling Systems UPP Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump 6/30/2025 6/30/2028
Leak Detect - Piping Sump Sensor with positive shutdown 6/30/2025 6/30/2028
Spill Contain Device Double Wall Spill Bucket 6/30/2025 6/30/2028
Tank Fiberglass Double Wall XERXES Not applicable Not applicable
Vent, Riser, Fill Piping Steel risers Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Franklin Fueling Systems UPP Precision Test (Piping) Pass 8/3/2022



Tank Number 6

Capacity: 14000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/10/2012 Abandoned Material:
Current Age: 13 Abandoned Date:
Install Date: 8/2/2012 Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date:

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Mechanical Other Non-vented check valve Not applicable Not applicable
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 6/29/2026 6/29/2027
Overfill Prev Device Overfill Alarm 6/30/2025 6/30/2028
Overfill Prev Device Overfill Drop Tube Valve 8/19/2025 8/19/2028
Piping Flexible Double Wall Franklin Fueling Systems UPP Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump 6/30/2025 6/30/2028
Leak Detect - Piping Sump Sensor with positive shutdown 6/30/2025 6/30/2028
Spill Contain Device Double Wall Spill Bucket 6/30/2025 6/30/2028
Tank Fiberglass Double Wall XERXES Not applicable Not applicable
Vent, Riser, Fill Piping Steel risers Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Franklin Fueling Systems UPP Precision Test (Piping) Pass 8/3/2022



Tank Number 7

Capacity: 6000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/10/2012 Abandoned Material:
Current Age: 13 Abandoned Date:
Install Date: 8/2/2012 Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date:

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Electronic Pressurized Line Leak Detection 6/29/2026 6/29/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 6/29/2026 6/29/2027
Overfill Prev Device Overfill Alarm 6/30/2025 6/30/2028
Overfill Prev Device Overfill Drop Tube Valve 8/19/2025 8/19/2028
Piping Flexible Double Wall Franklin Fueling Systems UPP Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump 6/30/2025 6/30/2028
Leak Detect - Piping Sump Sensor with positive shutdown 6/30/2025 6/30/2028
Spill Contain Device Double Wall Spill Bucket 6/30/2025 6/30/2028
Tank Fiberglass Double Wall XERXES Not applicable Not applicable
Vent, Riser, Fill Piping Steel risers Not applicable Not applicable

Additional Tests

No Tests Listed




Tank Number 8

Capacity: 30000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/15/2023 Abandoned Material:
Current Age: 2 Abandoned Date:
Install Date: 10/16/2023 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 12/13/2023

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Electronic Pressurized Line Leak Detection 6/29/2026 6/29/2027
Leak Detect - Tank Automatic Tank Gauging Incon TS 550 EVO 6/29/2026 6/29/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 6/29/2026 6/29/2027
Overfill Prev Device Overfill Alarm 7/2/2025 7/2/2028
Overfill Prev Device Overfill Drop Tube Valve 6/30/2025 6/30/2028
Overfill Prev Device Overfill Drop Tube Valve 6/30/2025 6/30/2028
Piping Flexible Double Wall Franklin Fueling Systems UPP Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump 6/30/2025 6/30/2028
Leak Detect - Piping Sump Sensor with positive shutdown 6/30/2025 6/30/2028
Spill Contain Device Double Wall Spill Bucket 6/30/2025 6/30/2028
Spill Contain Device Double Wall Spill Bucket 6/30/2025 6/30/2028
Tank Fiberglass Double Wall KBK Industries Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Franklin Fueling Systems UPP Precision Test (Piping) Pass 2/2/2024
Tank Fiberglass Double Wall KBK Industries Precision Test (Tank) Pass 2/2/2024



Tank Number 9

Capacity: 6000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/15/2023 Abandoned Material:
Current Age: 2 Abandoned Date:
Install Date: 10/20/2023 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 12/13/2023

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Composite Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Electronic Pressurized Line Leak Detection 6/29/2026 6/29/2027
Leak Detect - Tank Automatic Tank Gauging Incon TS 550 EVO 6/29/2026 6/29/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 6/29/2026 6/29/2027
Overfill Prev Device Overfill Alarm 7/2/2025 7/2/2028
Overfill Prev Device Overfill Drop Tube Valve 6/30/2025 6/30/2028
Piping Flexible Double Wall Franklin Fueling Systems UPP Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump 6/30/2025 6/30/2028
Leak Detect - Piping Sump Sensor with positive shutdown 6/30/2025 6/30/2028
Spill Contain Device Double Wall Spill Bucket 6/30/2025 6/30/2028
Tank Fiberglass Double Wall KBK Industries Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Franklin Fueling Systems UPP Precision Test (Piping) Pass 2/2/2024
Tank Fiberglass Double Wall KBK Industries Precision Test (Tank) Pass 2/2/2024



Tank Number 10

Capacity: 6000 Petroleum Use:
Product: E85 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/15/2023 Abandoned Material:
Current Age: 2 Abandoned Date:
Install Date: 10/20/2023 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 12/13/2023

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Composite Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Electronic Pressurized Line Leak Detection 6/29/2026 6/29/2027
Leak Detect - Tank Automatic Tank Gauging Incon TS 550 EVO 6/29/2026 6/29/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 6/29/2026 6/29/2027
Overfill Prev Device Overfill Alarm 7/2/2025 7/2/2028
Overfill Prev Device Overfill Drop Tube Valve 6/30/2025 6/30/2028
Piping Flexible Double Wall Franklin Fueling Systems UPP Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump 6/30/2025 6/30/2028
Leak Detect - Piping Sump Sensor with positive shutdown 6/30/2025 6/30/2028
Spill Contain Device Double Wall Spill Bucket 6/30/2025 6/30/2028
Tank Fiberglass Double Wall KBK Industries Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Franklin Fueling Systems UPP Precision Test (Piping) Pass 2/2/2024
Tank Fiberglass Double Wall KBK Industries Precision Test (Tank) Pass 2/2/2024

Failed test = the latest test has failed.

Not applicable = a test does not apply to this equipment type or configuration.

No passing test found = a passing test is expected but was not found from the source data.


Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/30/2025 6/30/2028
Leak Detect - Piping Sump Sensor with positive shutdown 6/29/2026 6/29/2027



Name\ID 11

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/30/2025 6/30/2028
Leak Detect - Piping Sump Sensor with positive shutdown 6/29/2026 6/29/2027



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/30/2025 6/30/2028
Leak Detect - Piping Sump Sensor 6/29/2026 6/29/2027



Name\ID 15/16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/30/2025 6/30/2028
Leak Detect - Piping Sump Sensor 6/29/2026 6/29/2027



Name\ID 17/18

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/30/2025 6/30/2028
Leak Detect - Piping Sump Sensor 6/29/2026 6/29/2027



Name\ID 19/20

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/30/2025 6/30/2028
Leak Detect - Piping Sump Sensor 6/29/2026 6/29/2027



Name\ID 21/22

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/30/2025 6/30/2028
Leak Detect - Piping Sump Sensor 6/29/2026 6/29/2027



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/30/2025 6/30/2028
Leak Detect - Piping Sump Sensor with positive shutdown 6/29/2026 6/29/2027



Name\ID 31/32

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/30/2025 6/30/2028
Leak Detect - Piping Sump Sensor with positive shutdown 6/29/2026 6/29/2027



Name\ID 33/34

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/30/2025 6/30/2028
Leak Detect - Piping Sump Sensor with positive shutdown 6/29/2026 6/29/2027



Name\ID 35/36

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/30/2025 6/30/2028
Leak Detect - Piping Sump Sensor with positive shutdown 6/29/2026 6/29/2027



Name\ID 37/38

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/30/2025 6/30/2028
Leak Detect - Piping Sump Sensor with positive shutdown 6/29/2026 6/29/2027



Name\ID 39/40

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/30/2025 6/30/2028
Leak Detect - Piping Sump Sensor with positive shutdown 6/29/2026 6/29/2027



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/30/2025 6/30/2028
Leak Detect - Piping Sump Sensor with positive shutdown 6/29/2026 6/29/2027



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/30/2025 6/30/2028
Leak Detect - Piping Sump Sensor with positive shutdown 6/29/2026 6/29/2027



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/30/2025 6/30/2028
Leak Detect - Piping Sump Sensor with positive shutdown 6/29/2026 6/29/2027

Failed test = the latest test has failed.

Not applicable = a test does not apply to this equipment type or configuration.

No passing test found = a passing test is expected but was not found from the source data.


MFD Motorfuel Dispensing Forms

Facility Number Name City Received Date Letter
2043141 Woodman's Gas/Lube & Car Wash North Aurora 06/28/2023 Letter Form