Notice of Violatlions (Current)
NOV Number:
E0020261321
(Pending)
Issue Date:
5/19/2026
Expiration Date:
7/18/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Dispenser 7/8 not functioning.
175.210 h)The attendant shall at all times be able to communicate with persons in the dispensing area. Repair or replace intercom. |
NOV Number:
E0020261322
(Pending)
Issue Date:
5/19/2026
Expiration Date:
7/18/2026
View NOV Form
| Tanks |
Violations |
| 1, 2 |
Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Tanks 1 and 2 STP sump support ring are rusted through. Containment support rings need to be replaced. |
| Facility |
Facility Operation and Maintenance Plan not completed or available. - Operations and Maintenance Template needs to be updated and kept on site. https://sfm.illinois.gov/ |
| Facility |
Missing copy of emergency instructions or emergency procedures plan - Emergency Procedures Plan needs to be updated and kept on site. https://sfm.illinois.gov/ |