Notice of Violatlions (Current)
NOV Number:
E0020261024
(Pending)
Issue Date:
4/16/2026
Expiration Date:
6/15/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Each emergency stop shall be identified by a sign on all-weather materials stating "EMERGENCY STOP" in 2 inch red capital letters - The emergency shut off switch on the north and south side exterior of the building needs another sign next to shut off switch. The existing signs are mounted high over the ice freezers. |
| Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - 175.210 h)The attendant shall at all times be able to communicate with persons in the dispensing area. Repair or replace intercom. |
NOV Number:
E0020261026
(Pending)
Issue Date:
4/16/2026
Expiration Date:
6/15/2026
View NOV Form
| Tanks |
Violations |
| 1, 2 |
Dispensers - hoses cracked, split or worn and require replacement - Replace main hose |
| Facility |
Miscellaneous - The emergency shut off switch on the south exterior of the building is blocked with a ice freezer. Freezer needs to be moved. |
| 1, 2, 3 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - 175.405 a) 1) A) Spill containment equipment that will prevent release of product to
the environment when the transfer hose is detached from the fill
pipe (e.g., a spill catch basin). Spill containment equipment shall
be maintained in a dry, clean state. |