Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2042636
Status: Active
Facility Name: DRAS Gas Station, LLC
Address: 247 E. Army Trail Rd. Bloomingdale, IL 60108
County: Du Page
Property Parcel: 02-23-305-032
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z000117
Green Tag Issue Date: 4/8/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: DRAS Real Estate, LLC
Owner Address: 247 E. Army Trail Rd. Bloomingdale, IL 60108
Owner Status: Current Owner
Purchase Date: 1/13/2025
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 8/20/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0041453 DRAS Real Estate, LLC Current Owner 1/13/2025
U0040052 Ramchandi, Inc. Former Owner 6/18/2020
U0034845 Bloomingdale Marathon Corp. Former Owner 11/14/2005
U0025560 Proviso Petroleum Company Former Owner 11/1/2005
U0035881 Army Trail Marathon Former Owner
U0017168 Stephan Bill Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020260385 (Pending)    Issue Date: 2/18/2026    Expiration Date: 4/19/2026    View NOV Form

Tanks Violations
Facility Financial responsibility must be reported yearly - Copy of UST insurance needs to be kept on site.
1 Line interstitial sensors have been raised and rendered inoperational. - Section 175.640 a)2) All new and existing sump sensors must be installed so as to detect liquid per manufacturer's specifications or, if not specified by the manufacturer, at the lowest point in the sump.
1 Miscellaneous - Exterior fill lid cracked.
Facility Missing copies of current testing certificates for operator training - All operator certificates need to be on site. There shall be at least one C operator on site at all times.
Facility Missing list of designated Class A/B & C Operators - This form can be found at https://sfm.illinois.gov/
1, 2 Piping interstitial must be open in all sumps - 175.420 b) Unless otherwise required by the manufacturer, the dispenser product piping sump jumper tubes shall be removed, or the product piping test boots pulled back after testing to allow the interstice to be open to the sump sensors. This is for all sumps.
1, 2 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - 175.405 a) 1) A) Spill containment equipment that will prevent release of product to the environment when the transfer hose is detached from the fill pipe (e.g., a spill catch basin). Spill containment equipment shall be maintained in a dry, clean state.

NOV Number: E0020260387 (Pending)    Issue Date: 2/18/2026    Expiration Date: 4/19/2026    View NOV Form

Tanks Violations
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - 175.210 h)The attendant shall at all times be able to communicate with persons in the dispensing area. Repair or replace intercom.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 12000 Gasoline - Regular Currently in use Federal $0.00
2 12000 Gasoline - Premium Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active

MFD Motorfuel Dispensing Forms