Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2042394
Status: Active
Facility Name: Grab & Go
Address: 1701 Kenosha Road Zion, IL 60099
County: Lake
Property Parcel: 04-18-400-047
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z000733
Green Tag Issue Date: 3/14/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: Grab & Go, Inc.
Owner Address: 1701 Kenosha Rd. Zion, IL 60099
Owner Status: Current Owner
Purchase Date: 9/5/2018
Type of Financial Responsibility: Certificate of Deposit
Financial Responsibility Reporting Due Date: 3/13/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0039348 Grab & Go, Inc. Current Owner 9/5/2018
U0038087 Zion Food Mart Former Operator
U0033548 R & A Petroleum Services, Inc. Former Owner / Operator 3/15/2005
U0030251 T-Mart, Inc. Former Owner / Operator

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020260757 (Pending)    Issue Date: 3/23/2026    Expiration Date: 5/22/2026    View NOV Form

Tanks Violations
Facility Fire Extinguishers - Past due for annual testing - Annual testing last completed Feb 2025

NOV Number: E0020260770 (Pending)    Issue Date: 3/23/2026    Expiration Date: 5/22/2026    View NOV Form

Tanks Violations
1, 2 Dispensers - hoses cracked, split or worn and require replacement
Facility Financial responsibility must be reported yearly - Financial Responsibility shall be declared annually; declaration form can be found at https://webapps.sfm.illinois.gov/USTPortal/forms/FinancialResponsibility. Complete form online and submit electronically.
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30-day Walkthrough Inspection shall be completed, and documentation maintained on site. 30-Day Walkthrough Inspection form available at www.sfm.illinois.gov. The form must be filled out by an A/B Operator, you must, initial each box that applies, date the form each month to ensure it is being done every 30 days, and the A/B operator must print and sign their name at the bottom. If more than one A/B operator fills out the form, then each must print and sign name at the bottom.
1, 2, 3 Required monthly tank leak test records not available. - Maintain one NORMAL/PASS report per TANK, per month, from tank monitor. (CSLD)
1, 2, 3 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
Facility Submit Notification Form For Ownership Change - Submit OSFM Notification Form showing change in facility ownership, complete and submit the online Notification for Underground Storage Tanks form which can be found at https://webapps.sfm.illinois.gov/USTPortal/NotificationForm
1, 2, 3 Tank precision test required. - Precision tank test is required due to missing or failed monthly monitoring (Per 41 Ill Admin code 175.630(c)(2))
1, 2 Water in containment without required sensors – install cathodic protection on all exposed steel piping or make containment watertight. By 10/13/28, all containments must be watertight and any CP installed in containments must be removed. - Dispensers 3/4 and 5/6 containment sump(s) contain(s) liquid. Remove liquid and repair containment to prevent further liquid ingress. Must provide documentaion showing repairs completed. (Per 41 Ill Admin code 175.410(h))

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 6/12/2006 Abandoned Material:
Current Age: 20 Abandoned Date:
Install Date: 8/11/2005 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/16/2006

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 3/3/2025 3/3/2028
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 3/19/2026 3/19/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 3/19/2026 3/19/2027
Overfill Prev Device Overfill Drop Tube Valve 3/19/2026 3/19/2029
Piping Flexible Double Wall A.P.T. Poly Tech N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Single Wall Spill Bucket 3/3/2025 3/3/2028
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech Precision Test (Piping) Pass 3/19/2026
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 4/13/2026



Tank Number 2

Capacity: 6000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 6/12/2006 Abandoned Material:
Current Age: 20 Abandoned Date:
Install Date: 8/11/2005 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/16/2006

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Cathodic Protection 3/26/2025 3/26/2028
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 3/19/2026 3/19/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 3/19/2026 3/19/2027
Overfill Prev Device Overfill Drop Tube Valve 3/19/2026 3/19/2029
Piping Flexible Double Wall A.P.T. Poly Tech N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Single Wall Spill Bucket 3/3/2025 3/3/2028
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech Precision Test (Piping) Pass 3/19/2026
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 4/13/2026



Tank Number 3

Capacity: 4000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 6/12/2006 Abandoned Material:
Current Age: 20 Abandoned Date:
Install Date: 8/11/2005 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/16/2006

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Cathodic Protection 3/26/2025 3/26/2028
Corrosion Prot - Piping Sacrificial Anode Flex Connector 3/26/2025 3/26/2028
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 3/19/2026 3/19/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 3/19/2026 3/19/2027
Overfill Prev Device Overfill Drop Tube Valve 3/19/2026 3/19/2029
Piping Flexible Double Wall A.P.T. Poly Tech N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Single Wall Spill Bucket 6/23/2025 6/23/2028
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech Precision Test (Piping) Pass 3/19/2026
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 4/13/2026

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A

MFD Motorfuel Dispensing Forms