Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2042188
Status: Active
Facility Name: Geneva Transportation Facility
Address: 38W700 Keslinger Road Geneva, IL 60134
County: Kane
Property Parcel:
Facility Type: School/College
Owner Type: Other Local
Green Tag Decal: Y003817
Green Tag Issue Date: 8/31/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Geneva CUSD #304
Owner Address: 227 N. 4th Street Geneva, IL 60134
Owner Status: Current Owner
Purchase Date: 6/8/2004
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 11/13/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Fleet 8/31/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0031989 Geneva CUSD #304 Current Owner 6/8/2004

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020252094 (Pending)    Issue Date: 8/14/2025    Expiration Date: 10/13/2025    View NOV Form

Tanks Violations
1, 2 Miscellaneous - UDC sumps require sensors installed.
1, 2 Piping interstitial must be open in all sumps - 175.420 b) Unless otherwise required by the manufacturer, the dispenser product piping sump jumper tubes shall be removed, or the product piping test boots pulled back after testing to allow the interstice to be open to the sump sensors. This is for all sumps.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 8000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/7/2004 Abandoned Material:
Current Age: 21 Abandoned Date:
Install Date: 6/8/2004 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 6/8/2004

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 8/29/2024 8/29/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 8/29/2024 8/29/2025
Overfill Prev Device Overfill Alarm 9/11/2024 9/11/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 8/29/2024 8/29/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/29/2024 8/29/2025
Spill Contain Device Double Wall Spill Bucket 8/6/2024 8/6/2027
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 8/29/2024
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 8/20/2024



Tank Number 2

Capacity: 2500 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/7/2004 Abandoned Material:
Current Age: 20 Abandoned Date:
Install Date: 6/8/2004 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 6/8/2005

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 8/29/2024 8/29/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 8/29/2024 8/29/2025
Overfill Prev Device Overfill Alarm 9/11/2024 9/11/2027
Overfill Prev Device Overfill Drop Tube Valve 9/11/2024 9/11/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 8/29/2024 8/29/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/29/2024 8/29/2025
Spill Contain Device Double Wall Spill Bucket 8/6/2024 8/6/2027
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 8/29/2024
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 8/20/2024

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/7/2021 6/7/2024
Leak Detect - Piping Sump Sensor with positive shutdown 6/21/2023 6/21/2024



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/7/2021 6/7/2024
Leak Detect - Piping Sump Sensor with positive shutdown 6/21/2023 6/21/2024

MFD Motorfuel Dispensing Forms

No Forms Found