Notice of Violations (Current)
NOV Number:
E0020261811
(Pending)
Issue Date:
7/15/2026
Expiration Date:
9/13/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Code complying instruction/warning signs are not properly mounted at each dispenser island - Dispenser 9/10 needs a warning sign. |
NOV Number:
E0020261812
(Pending)
Issue Date:
7/15/2026
Expiration Date:
9/13/2026
View NOV Form
| Tanks |
Violations |
| 1, 2 |
Line interstitial sensors have been raised and rendered inoperational. - Dispenser 3/4, 5/6, and T1 Premium STP sump have raised sensors. 175.640 a) 2) All new and existing sump sensors must be installed so as to detect liquid per manufacturer's specifications or, if not specified by the manufacturer, at the lowest point in the sump. |
IEMA Numbers Associated with the Facility
No IEMA Numbers Found
LUST
Fund Eligibility and Deductibility Determinations
No Applications Found
Tank Number 1
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Premium |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
11/20/2003 |
|
Abandoned Material: |
|
| Current Age: |
22 |
|
Abandoned Date: |
|
| Install Date: |
7/1/2003 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
11/4/2003 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
7/30/2025 |
7/30/2026 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors With Monitor |
7/30/2025 |
7/30/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
7/30/2025 |
7/30/2028 |
|
Piping
|
Flexible Double Wall Environ Geo Flex |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
10/5/2023 |
10/5/2026 |
Leak Detect - Piping
|
Sump Sensor |
10/5/2023 |
10/5/2026 |
|
Spill Contain Device
|
Double Wall Spill Bucket |
7/30/2025 |
7/30/2028 |
|
Tank
|
Fiberglass Double Wall XERXES |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall Environ Geo Flex
|
Precision Test (Piping)
|
Pass
|
8/19/2025
|
Tank Number 2
| Capacity: |
15000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
11/20/2003 |
|
Abandoned Material: |
|
| Current Age: |
22 |
|
Abandoned Date: |
|
| Install Date: |
7/1/2003 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
11/4/2003 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
7/7/2026 |
7/7/2027 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors With Monitor |
8/18/2025 |
8/18/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
7/30/2025 |
7/30/2028 |
|
Piping
|
Flexible Double Wall Environ Geo Flex |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
10/5/2023 |
10/5/2026 |
Leak Detect - Piping
|
Sump Sensor |
10/5/2023 |
10/5/2026 |
|
Spill Contain Device
|
Double Wall Spill Bucket |
7/30/2025 |
7/30/2028 |
|
Tank
|
Fiberglass Double Wall XERXES |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall Environ Geo Flex
|
Precision Test (Piping)
|
Pass
|
8/19/2025
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found