Notice of Violations (Current)
NOV Number:
E0020261811
(Pending)
Issue Date:
7/15/2026
Expiration Date:
9/13/2026
| Tanks |
Violations |
| Facility |
Code complying instruction/warning signs are not properly mounted at each dispenser island - Dispenser 9/10 needs a warning sign. |
NOV Number:
E0020261812
(Pending)
Issue Date:
7/15/2026
Expiration Date:
9/13/2026
| Tanks |
Violations |
| 1, 2 |
Line interstitial sensors have been raised and rendered inoperational. - Dispenser 3/4, 5/6, and T1 Premium STP sump have raised sensors. 175.640 a) 2) All new and existing sump sensors must be installed so as to detect liquid per manufacturer's specifications or, if not specified by the manufacturer, at the lowest point in the sump. |