Notice of Violations (Current)
NOV Number:
E0020260534
(Pending)
Issue Date:
3/3/2026
Expiration Date:
5/2/2026
View NOV Form
| Tanks |
Violations |
| 2 |
Drop tube valve or overfill alarm failed inspection. Repair or replace equipment. - Section 175.405 Spill Containment and Overfill Prevention Equipment
c) Overfill prevention equipment must be inspected at installation, immediately after any repairs, and at least once every three years, and the inspection shall meet the following criteria:
1) At a minimum, the inspection must ensure that overfill prevention equipment is set to activate at the correct level specified in subsection (a);
2) The overfill prevention equipment will activate when the regulated
substance reaches that level; and
3) Inspections must be conducted in accordance with inspection requirements
developed by the manufacturer. |
IEMA Numbers Associated with the Facility
No IEMA Numbers Found
LUST
Fund Eligibility and Deductibility Determinations
No Applications Found
Tank Number 1
| Capacity: |
15000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
6/19/2003 |
|
Abandoned Material: |
|
| Current Age: |
23 |
|
Abandoned Date: |
|
| Install Date: |
3/1/2003 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
6/5/2003 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
12/2/2025 |
12/2/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350R |
3/10/2026 |
3/10/2027 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
2/12/2026 |
2/12/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
12/2/2025 |
12/2/2028 |
|
Piping
|
Flexible Double Wall |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
1/26/2024 |
1/26/2027 |
Leak Detect - Piping
|
Sump Sensor |
1/26/2024 |
1/26/2027 |
|
Spill Contain Device
|
Double Wall Spill Bucket |
12/2/2025 |
12/2/2028 |
|
Tank
|
Fiberglass Double Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors
|
Sensor Functional
|
Pass
|
1/18/2010
|
|
Leak Detect - Piping
|
Sump Sensor
|
Sensor Functional
|
Pass
|
1/18/2010
|
Tank Number 2
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Premium |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
6/19/2003 |
|
Abandoned Material: |
|
| Current Age: |
23 |
|
Abandoned Date: |
|
| Install Date: |
3/1/2003 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
6/5/2003 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
12/2/2025 |
12/2/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350R |
12/2/2025 |
12/2/2026 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
2/12/2026 |
2/12/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
5/5/2026 |
5/5/2029 |
|
Piping
|
Flexible Double Wall |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
1/26/2024 |
1/26/2027 |
Leak Detect - Piping
|
Sump Sensor |
1/26/2024 |
1/26/2027 |
|
Spill Contain Device
|
Double Wall Spill Bucket |
12/2/2025 |
12/2/2028 |
|
Tank
|
Fiberglass Double Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors
|
Sensor Functional
|
Pass
|
1/18/2010
|
|
Leak Detect - Piping
|
Sump Sensor
|
Sensor Functional
|
Pass
|
1/18/2010
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found