Facility Details

Facility Number: 2041376
Status: Active
Facility Name: 7-Eleven Store #33346
Address: 950 North Rohlwing Road Itasca, IL 60143
County: Du Page
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z000113
Green Tag Issue Date: 3/26/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: 7-Eleven, Inc.
Owner Address: 3200 Hackberry Road - Gas Compliance Irving, TX 75063
Owner Status: Current Owner
Purchase Date: 1/1/2001
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 12/8/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0014207 7-Eleven, Inc. Current Owner 1/1/2001

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020260533 (Pending)    Issue Date: 3/3/2026    Expiration Date: 5/2/2026    View NOV Form

Tanks Violations
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - 175.210 h)The attendant shall at all times be able to communicate with persons in the dispensing area. Repair or replace intercom.

NOV Number: E0020260534 (Pending)    Issue Date: 3/3/2026    Expiration Date: 5/2/2026    View NOV Form

Tanks Violations
2 Drop tube valve or overfill alarm failed inspection. Repair or replace equipment. - Section 175.405 Spill Containment and Overfill Prevention Equipment c) Overfill prevention equipment must be inspected at installation, immediately after any repairs, and at least once every three years, and the inspection shall meet the following criteria: 1) At a minimum, the inspection must ensure that overfill prevention equipment is set to activate at the correct level specified in subsection (a); 2) The overfill prevention equipment will activate when the regulated substance reaches that level; and 3) Inspections must be conducted in accordance with inspection requirements developed by the manufacturer.
2 Line interstitial sensors have been raised and rendered inoperational. - T2 Premium STP sump has a raised sensor. 175.640 a) 2) All new and existing sump sensors must be installed so as to detect liquid per manufacturer's specifications or, if not specified by the manufacturer, at the lowest point in the sump.
Facility Miscellaneous - Emergency shut off switch at the control station needs to be unobstructed. 175.210 d) 3) Equipped with an emergency stop at all control stations, which shall be conspicuously marked and readily accessible to the attendant, whether or not the control station is less than 20 feet from any dispenser or a security booth is provided for the attendant. The emergency stop shall be located in a position to allow all dispensing devices to be readily visible to the attendant, or as approved by OSFM. Each emergency stop shall be identified by a sign on all-weather materials stating "EMERGENCY STOP" in 2 inch red capital letters.
1, 2 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - 175.405 a) 1) A) Spill containment equipment that will prevent release of product to the environment when the transfer hose is detached from the fill pipe (e.g., a spill catch basin). Spill containment equipment shall be maintained in a dry, clean state.
1 Tank monitor does not appear to function properly and requires maintenance. - ATG failed annual inspection on 2/12/26. Retest ATG and enter passing results on OSFM portal.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 15000 Gasoline - Regular Currently in use Federal $0.00
2 10000 Gasoline - Premium Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active
9/10 Active
11/12 Active