Drop tube valve or overfill alarm failed inspection. Repair or replace equipment. - Section 175.405 Spill Containment and Overfill Prevention Equipment
c) Overfill prevention equipment must be inspected at installation, immediately after any repairs, and at least once every three years, and the inspection shall meet the following criteria:
1) At a minimum, the inspection must ensure that overfill prevention equipment is set to activate at the correct level specified in subsection (a);
2) The overfill prevention equipment will activate when the regulated
substance reaches that level; and
3) Inspections must be conducted in accordance with inspection requirements
developed by the manufacturer. |
| 2 |
Line interstitial sensors have been raised and rendered inoperational. - T2 Premium STP sump has a raised sensor.
175.640 a) 2) All new and existing sump sensors must be installed so as to detect liquid per manufacturer's specifications or, if not specified by the manufacturer, at the lowest point in the sump. |
| Facility |
Miscellaneous - Emergency shut off switch at the control station needs to be unobstructed.
175.210 d) 3) Equipped with an emergency stop at all control stations, which shall be
conspicuously marked and readily accessible to the attendant, whether or
not the control station is less than 20 feet from any dispenser or a security
booth is provided for the attendant. The emergency stop shall be located
in a position to allow all dispensing devices to be readily visible to the
attendant, or as approved by OSFM. Each emergency stop shall be
identified by a sign on all-weather materials stating "EMERGENCY
STOP" in 2 inch red capital letters. |
| 1, 2 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - 175.405 a) 1) A) Spill containment equipment that will prevent release of product to
the environment when the transfer hose is detached from the fill
pipe (e.g., a spill catch basin). Spill containment equipment shall
be maintained in a dry, clean state. |
| 1 |
Tank monitor does not appear to function properly and requires maintenance. - ATG failed annual inspection on 2/12/26. Retest ATG and enter passing results on OSFM portal. |