Notice of Violations (Current)
NOV Number:
E0020261967
(Pending)
Issue Date:
8/4/2026
Expiration Date:
10/3/2026
View NOV Form
| Tanks |
Violations |
| 1, 2, 3 |
Line leak detection equipment in alarm or failed test, must repair or replace. - 7-23-26 your testing contractor failed the sump sensors located in the STP's and dispensers. They are not programmed for positive shut-down and the identifications for those sensors are not identified properly when alarm is trigured in the tank monitor. Must re-identify. |
| 1 |
Miscellaneous - Must submit to inspector the amount of the release from your reconsiliation when the dispenser was struck. |