Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2041162
Status: Active
Facility Name: Bensenville Fuel Mark
Address: 1188 W. Foster Ave. Bensenville, IL 60106
County: Du Page
Property Parcel: 03-11-300-001
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z000216
Green Tag Issue Date: 7/3/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: GPM Midwest, LLC
Owner Address: 8565 Magellan Pkwy, Ste. 400 Richmond, VA 23227
Owner Status: Current Owner
Purchase Date: 3/19/2015
Type of Financial Responsibility: Surety Bond
Financial Responsibility Reporting Due Date: 4/29/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0037728 GPM Midwest, LLC Current Owner 3/19/2015
U0033990 Road Ranger, LLC Former Owner 6/23/2011
U0035000 My Cooki Corp. Former Owner 2/8/2008
U0034614 Kingery Group, Inc. Former Owner 10/1/2003
U0030770 Alpha / Omega LLC Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020261220 (Pending)    Issue Date: 5/7/2026    Expiration Date: 7/6/2026    View NOV Form

Tanks Violations
Facility Code complying instruction/warning signs are not properly mounted at each dispenser island - 175.220 a) Minimum signage requires letters shall not be less than 7/8” in height. The top of the sign shall be mounted no higher than 10’ above grade. The wording shall include a minimum of 1) “Warning” 2) “Stop Engine” 3) “No Smoking” 4) “Persons fueling vehicles shall remain with their vehicle, at the nozzle, while fueling is in progress” 5) “It is unlawful and dangerous for anyone to dispense gasoline into unapproved containers”
Facility Each emergency stop shall be identified by a sign on all-weather materials stating "EMERGENCY STOP" in 2 inch red capital letters - 175.210 d) 3) Equipped with an emergency stop at all control stations, which shall be conspicuously marked and readily accessible to the attendant, whether or not the control station is less than 20 feet from any dispenser or a security booth is provided for the attendant. The emergency stop shall be located in a position to allow all dispensing devices to be readily visible to the attendant, or as approved by OSFM. Each emergency stop shall be identified by a sign on all-weather materials stating "EMERGENCY STOP" in 2 inch red capital letters.

NOV Number: E0020261221 (Pending)    Issue Date: 5/7/2026    Expiration Date: 7/6/2026    View NOV Form

Tanks Violations
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - Emergency shut off switch needs annual testing performed. OSFM form shall be kept on site.
1, 2 Line interstitial sensors have been raised and rendered inoperational. - Dispenser sump sensor 5/6 is lying sideways. Section 175.640 a)2) All new and existing sump sensors must be installed so as to detect liquid per manufacturer's specifications or, if not specified by the manufacturer, at the lowest point in the sump.
1 Miscellaneous - Dispenser 7/8 has a slight leak under the dispenser. Check dispenser 1/2 and T1 STP sump for leaks.
2 Miscellaneous - ATG has L2 Fuel Alarm showing
2, 3 Miscellaneous - Dispenser 7/8 has a slight leak under the dispenser. Check dispenser 1/2 and T1 STP sump for leaks.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual walkthrough needs to be performed. OSFM form shall be completed and kept on site.
1, 2, 3 Precision line test required. - Multiple monthly sensor reports have sensors in alarm.
1, 2, 3 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Shear valves need annual testing performed. OSFM form shall be completed and kept on site.
2, 3 Tank interstitial sensors in alarm or failed test, must repair or replace. - On 11/24/25 Protanic failed both non-discriminating interstitial monitoring sensors. Repair and or replace sensors and retest.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 15000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/20/2003 Abandoned Material:
Current Age: 23 Abandoned Date:
Install Date: 10/2/2002 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 3/6/2003

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 11/24/2025 11/24/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 11/24/2025 11/24/2026
Overfill Prev Device Overfill Drop Tube Valve 12/10/2024 12/10/2027
Piping Flexible Double Wall Environ Geo Flex N/A N/A
Piping Single Wall STP/Tanktop Sump 3/7/2024 3/7/2027
Leak Detect - Piping Sump Sensor 11/24/2025 11/24/2026
Spill Contain Device Double Wall Spill Bucket 6/14/2024 6/14/2027
Tank Composite Double Wall Modern Welding Glasteel II N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Environ Geo Flex Precision Test (Piping) Pass 11/24/2025
Tank Composite Double Wall Modern Welding Glasteel II Precision Test (Tank) Pass 5/9/2024



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/20/2003 Abandoned Material:
Current Age: 23 Abandoned Date:
Install Date: 10/2/2002 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 3/6/2003

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 11/24/2025 11/24/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 12/10/2024 12/10/2025
Overfill Prev Device Overfill Drop Tube Valve 12/10/2024 12/10/2027
Piping Flexible Double Wall Environ Geo Flex N/A N/A
Piping Single Wall STP/Tanktop Sump 3/7/2024 3/7/2027
Leak Detect - Piping Sump Sensor 11/24/2025 11/24/2026
Spill Contain Device Single Wall Spill Bucket 3/7/2024 3/7/2027
Tank Composite Double Wall Modern Welding Glasteel II N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Environ Geo Flex Precision Test (Piping) Pass 11/24/2025
Tank Composite Double Wall Modern Welding Glasteel II Precision Test (Tank) Pass 5/9/2024



Tank Number 3

Capacity: 10000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/20/2003 Abandoned Material:
Current Age: 23 Abandoned Date:
Install Date: 10/2/2002 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 3/6/2003

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 11/24/2025 11/24/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 12/10/2024 12/10/2025
Overfill Prev Device Overfill Drop Tube Valve 12/10/2024 12/10/2027
Piping Flexible Double Wall Environ Geo Flex N/A N/A
Piping Single Wall STP/Tanktop Sump 3/7/2024 3/7/2027
Leak Detect - Piping Sump Sensor 11/24/2025 11/24/2026
Spill Contain Device Single Wall Spill Bucket 3/7/2024 3/7/2027
Tank Composite Double Wall Modern Welding Glasteel II N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Environ Geo Flex Precision Test (Piping) Pass 11/24/2025
Tank Composite Double Wall Modern Welding Glasteel II Precision Test (Tank) Pass 5/9/2024

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/7/2024 3/7/2027
Leak Detect - Piping Sump Sensor 11/24/2025 11/24/2026



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/7/2024 3/7/2027
Leak Detect - Piping Sump Sensor 11/24/2025 11/24/2026



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/7/2024 3/7/2027
Leak Detect - Piping Sump Sensor 11/24/2025 11/24/2026



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/7/2024 3/7/2027
Leak Detect - Piping Sump Sensor 11/24/2025 11/24/2026

MFD Motorfuel Dispensing Forms