Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2040961
Status: Active
Facility Name: I O M Services (Mobil)
Address: 4540 S Pulaski Ave.
Chicago, IL 60632
County: Cook
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X002027
Green Tag Issue Date: 6/16/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: I O M, Inc.
Owner Address: 4540 S Pulaski Ave.
Chicago, IL 60632
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Letter of Credit
Financial Responsibility Reporting Due Date: 12/13/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 6/17/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0030604 I O M, Inc., Current Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020241328 (Pending)    Issue Date: 5/8/2024    Expiration Date: 7/7/2024    View NOV Form

Tanks Violation
Facility Missing copies of 30 day Walkthrough Inspection Report.
Facility Missing copy of emergency instructions or emergency procedures plan
Facility Missing copy of written UST facility operation & maintenance plan
1, 2, 3 Tank monitor does not appear to function properly and requires maintenance.
1, 2, 3 Triennial testing for qualifying piping containment sump not completed (Required every 3 years).

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/7/2002 Abandoned Material:
Current Age: 22 Abandoned Date:
Install Date: 9/19/2001 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/24/2024 4/24/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 3/29/2023 3/29/2024
Overfill Prev Device Overfill Drop Tube Valve 3/29/2023 3/29/2026
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 3/25/2021 3/25/2024
Leak Detect - Piping Non-Discriminating Sump Sensor 5/22/2019 5/22/2020
Spill Contain Device Single Wall Spill Bucket 4/24/2024 4/24/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test Pass 4/24/2024



Tank Number 2

Capacity: 12000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/7/2002 Abandoned Material:
Current Age: 22 Abandoned Date:
Install Date: 9/19/2001 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/24/2024 4/24/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 3/29/2023 3/29/2024
Overfill Prev Device Overfill Drop Tube Valve 3/29/2023 3/29/2026
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 6/2/2022 6/2/2025
Leak Detect - Piping Non-Discriminating Sump Sensor 5/22/2019 5/22/2020
Spill Contain Device Single Wall Spill Bucket 4/24/2024 4/24/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test Pass 4/24/2024



Tank Number 3

Capacity: 8000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/7/2002 Abandoned Material:
Current Age: 22 Abandoned Date:
Install Date: 9/19/2001 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/24/2024 4/24/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 3/29/2023 3/29/2024
Overfill Prev Device Overfill Drop Tube Valve 3/29/2023 3/29/2026
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 3/25/2021 3/25/2024
Leak Detect - Piping Non-Discriminating Sump Sensor 5/22/2019 5/22/2020
Spill Contain Device Single Wall Spill Bucket 4/24/2024 4/24/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test Pass 4/24/2024

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 4/24/2024 4/24/2027
Leak Detect - Piping Sump Sensor 4/24/2024 4/24/2025



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/7/2024 6/7/2027
Leak Detect - Piping Sump Sensor with positive shutdown 4/24/2024 4/24/2025



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 4/24/2024 4/24/2027
Leak Detect - Piping Sump Sensor 4/24/2024 4/24/2025



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 4/24/2024 4/24/2027
Leak Detect - Piping Sump Sensor 4/24/2024 4/24/2025



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/24/2024 4/24/2027
Leak Detect - Piping Sump Sensor with positive shutdown 4/24/2024 4/24/2025



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/24/2024 4/24/2027
Leak Detect - Piping Sump Sensor with positive shutdown 4/24/2024 4/24/2025

MFD Motorfuel Dispensing Forms