Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2040632
Status: Active
Facility Name: First Student, Inc. #12348
Address: 19200 Chicago Heights Glenwood Road Glenwood, IL 60425
County: Cook
Property Parcel: 32-09-100-017-0000
Facility Type: Private Institution
Owner Type: Private
Green Tag Decal: Z003717
Green Tag Issue Date: 12/12/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Fleet

Owner Details

Owner Name: First Group America
Owner Address: 191 Rosa Parks Street 8th Floor Cincinnati, OH 45202
Owner Status: Current Owner
Purchase Date: 9/30/2008
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 7/29/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0028964 First Group America Current Owner 9/30/2008
U0030276 First Student, Inc. Former Owner 9/30/2008

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020260793 (Pending)    Issue Date: 3/25/2026    Expiration Date: 5/24/2026    View NOV Form

Tanks Violations
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all dispensers. Form can be found at https://sfm.illinois.gov to download and complete.
Facility Financial responsibility must be reported yearly - The form can be found at: https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility. (Submit this form after the change of ownership notification form has been approved.)
Facility Missing copies of 30 day Walkthrough Inspection Report. - Shall be completed, and documentation maintained on site. 30-Day Walkthrough Inspection form available at https://sfm.illinois.gov/content/dam/soi/en/web/sfm/sfmdocuments/documents/30-day-walkthrough-inspection-report.pdf
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough shall be performed by a licensed contractor shall be conducted and documentation maintained on site.
1 Required monthly tank interstitial sensor records not available. - Maintain one NORMAL report per TANK, per month, from ATG.
1 Required monthly tank leak test records not available. - Maintain one PASSING report per TANK, per month, from ATG. Reference 175.630 c)2)B)
1 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
Facility Submit Notification Form For Ownership Change - The Notification Form is available at https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. Select “New Owner” as the type of notification form. ( Make sure you write down the access Code that is given to you when you start the notification form.) Owner has to match as it appears on the deed.
1 Tank interstitial sensor functional test not accomplished (Required annually).
1 Tank precision test required. - Tank precision required due to missing monthly passing tapes.
1 Water in containment without required sensors – install cathodic protection on all exposed steel piping or make containment watertight. By 10/13/28, all containments must be watertight and any CP installed in containments must be removed. - Will need documentation showing that containment has been fixed along with test results.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 12000 Diesel Fuel Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active

MFD Motorfuel Dispensing Forms

No Forms Found