Notice of Violatlions (Current)
NOV Number:
E0020260864
(Pending)
Issue Date:
4/1/2026
Expiration Date:
5/31/2026
| Tanks |
Violations |
| 2 |
Drop tube valve or overfill alarm failed inspection. Repair or replace equipment. - Triennial inspection/testing of overfill device (drop tube valve) failed. Repair/replace as necessary; device(s) shall be retested with passing results and uploaded to OSFM website. |
| 2 |
Tank interstitial sensors in alarm or failed test, must repair or replace. - Annual leak detection certification (Interstitial Sensors) failed testing 3/17/2026. Repair/replace as necessary. Retesting shall be completed, and submitted to OSFM via the contractor portal. Maintain passing test documentation on site for 2 years. |