Notice of Violatlions (Current)
NOV Number:
E0020260678
(Pending)
Issue Date:
3/13/2026
Expiration Date:
5/12/2026
View NOV Form
| Tanks |
Violations |
| Facility |
A/B operator retraining required as a result of issuance of the Notice of Violation and must be completed within 30 days. |
| Facility |
Control station not equipped with an emergency shutoff switch - SWITCH MUST BE ACCESSIBLE AND MARKED |
| 3 |
Line leak detection equipment in alarm or failed test, must repair or replace. - SENSOR IN ALARM |
| Facility |
Missing copies of 30 day Walkthrough Inspection Report. |
| 1, 2, 3 |
Required monthly tank interstitial sensor records not available. |
| 1, 2, 3 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
| 1, 2, 3 |
Tank monitor does not appear to function properly and requires maintenance. - IN ALARM |
| 1, 2, 3 |
Tank precision test required. |
| 1, 2, 3 |
Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - ALL 3 STP CONTAINMENTS PAST DUE FOR TESTING |
NOV Number:
E0020260681
(Pending)
Issue Date:
3/13/2026
Expiration Date:
5/12/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - PLEASE REPAIR OR REPLACE INTERCOM |
| Facility |
Fire Extinguishers - 2 4A:60BC extinguishers not provided, 1 at or near control station and 1 in the dispensing areas - ONLY 1 EXTINGUISHER ON SITE |
| Facility |
Miscellaneous - EMERGENCY SWITCH BEHIND THE COUNTER MUST BE ACCESSIBLE AND MARKED |
NOV Number:
E0020260691
(Pending)
Issue Date:
3/16/2026
Expiration Date:
5/15/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Financial responsibility must be reported yearly - https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility |
| Facility |
Submit Notification Form For Ownership Change - https://webapps.sfm.illinois.gov/USTPortal/NotificationForm |