11, 12, 13 |
Dispensers - hoses cracked, split or worn and require replacement - Replace dispenser 1 Diesel whip and dispenser 5 main hose. |
Facility |
Electrical Does Not Comply - Open electric at NE corner emergency stop. |
Facility |
Miscellaneous - Emergency stop shall be readily accessible and conspicuously marked by a sign on all-weather materials stating "EMERGENCY STOP" in 2 inch red capital letters. (Per 41 Ill Admin code 175.210.d.3)
No signage for emergency stop next to ice machines. |
16 |
Overfill alarm does not appear to function properly. - Overfill alarm is not functional; repair/replace as necessary to insure functionality.
Alarm has no sound. |
11, 12, 13, 14, 15 |
Piping interstitial must be open in all sumps - Remove jumper tubing or place tubing in orientation to allow liquid to leave secondary piping and enter sump. (Per 41 Ill Admin code 175.420.b(b).) |
11, 12, 13, 14, 15, 16 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |