Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2039882
Status: Active
Facility Name: Circle K #6839
Address: 3153 West 183rd Homewood, IL 604302806
County: Cook
Property Parcel: 31-01-100-016-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z001320
Green Tag Issue Date: 8/14/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: RDK Ventures LLC
Owner Address: 1120 W. Warner Rd. Tempe, AZ 85284
Owner Status: Current Owner
Purchase Date: 11/7/2011
Type of Financial Responsibility: Guarantee
Financial Responsibility Reporting Due Date: 10/27/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0035671 RDK Ventures LLC Current Owner 11/7/2011
U0033587 Jetco Properties, Inc. Former Owner 6/2/2006
U0028677 Albertson's, Inc. Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020260584 (Pending)    Issue Date: 3/6/2026    Expiration Date: 5/5/2026    View NOV Form

Tanks Violations
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers. Reference 175.210 h) (No Coms are available.
Facility Fire Extinguishers - Past due for annual testing - Last tested was Aug. 2024. Needs to be tested annually.

NOV Number: E0020260585 (Pending)    Issue Date: 3/6/2026    Expiration Date: 5/5/2026    View NOV Form

Tanks Violations
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - Inside emergency stop was not tested. Only outside E-stops were tested according to testing reports.
1 Install or replace lockable fill pipe caps. - Gasket is missing from Regular fill snap cap. Repair/replace cap.
1, 2 Line interstitial sensors have been raised and rendered inoperational. - (Regular STP and Dispenser 3/4)
1, 2 Miscellaneous - Equipment in disrepair 176.410 (Dispenser 3/4 Sensor)
1 Open electrical conduit or junction boxes. - Junction box on RUL ATG is off exposing wires. Repair/replace cap.
1 Piping interstitial must be open in all sumps - (Closed in Rul STP. )
1, 2 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 15000 Gasoline - Regular Currently in use Federal $0.00
2 10000 Gasoline - Premium Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active

MFD Motorfuel Dispensing Forms