Notice of Violations (Current)
No Notice of Violations Found
IEMA Numbers Associated with the Facility
No IEMA Numbers Found
LUST
Fund Eligibility and Deductibility Determinations
No Applications Found
Tank Number 1
| Capacity: |
6000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
E-85 |
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
12/6/2000 |
|
Abandoned Material: |
|
| Current Age: |
25 |
|
Abandoned Date: |
|
| Install Date: |
6/1/2000 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
10/24/2000 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
9/30/2025 |
9/30/2028 |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
9/30/2025 |
9/30/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging OPW Site Sentinel Integra 100 |
9/30/2025 |
9/30/2026 |
|
Leak Detect - Tank
|
Hydrostatic Reservoir Interstitial Monitoring Sensors |
9/30/2025 |
9/30/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
8/23/2024 |
8/23/2027 |
|
Piping
|
Fiberglass Double Wall Ameron |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
8/23/2024 |
8/23/2027 |
Leak Detect - Piping
|
Sump Sensor |
8/23/2024 |
8/23/2027 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
8/23/2024 |
8/23/2027 |
|
Tank
|
Fiberglass Brine Filled Double Wall XERXES |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Double Wall Ameron
|
Precision Test (Piping)
|
Pass
|
1/11/2022
|
Tank Number 2
| Capacity: |
6000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
12/6/2000 |
|
Abandoned Material: |
|
| Current Age: |
25 |
|
Abandoned Date: |
|
| Install Date: |
6/1/2000 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
10/24/2000 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
9/30/2025 |
9/30/2028 |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
9/30/2025 |
9/30/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging OPW Site Sentinel Integra 100 |
9/30/2025 |
9/30/2026 |
|
Leak Detect - Tank
|
Hydrostatic Reservoir Interstitial Monitoring Sensors |
9/30/2025 |
9/30/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
8/23/2024 |
8/23/2027 |
|
Piping
|
Fiberglass Double Wall Ameron |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
8/23/2024 |
8/23/2027 |
Leak Detect - Piping
|
Sump Sensor |
8/23/2024 |
8/23/2027 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
8/23/2024 |
8/23/2027 |
|
Tank
|
Fiberglass Brine Filled Double Wall XERXES |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Double Wall Ameron
|
Precision Test (Piping)
|
Pass
|
7/28/2021
|
Tank Number 3
| Capacity: |
6000 |
|
Petroleum Use: |
|
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
12/6/2000 |
|
Abandoned Material: |
|
| Current Age: |
25 |
|
Abandoned Date: |
|
| Install Date: |
6/1/2000 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
10/24/2000 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
9/30/2025 |
9/30/2028 |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
9/30/2025 |
9/30/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging OPW Site Sentinel Integra 100 |
9/30/2025 |
9/30/2026 |
|
Leak Detect - Tank
|
Hydrostatic Reservoir Interstitial Monitoring Sensors |
9/30/2025 |
9/30/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
8/23/2024 |
8/23/2027 |
|
Piping
|
Fiberglass Double Wall Ameron |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
8/23/2024 |
8/23/2027 |
Leak Detect - Piping
|
Sump Sensor |
8/23/2024 |
8/23/2027 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
8/23/2024 |
8/23/2027 |
|
Tank
|
Fiberglass Brine Filled Double Wall XERXES |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Double Wall Ameron
|
Precision Test (Piping)
|
Pass
|
7/28/2021
|
Tank Number 4
| Capacity: |
6000 |
|
Petroleum Use: |
|
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
12/6/2000 |
|
Abandoned Material: |
|
| Current Age: |
25 |
|
Abandoned Date: |
|
| Install Date: |
6/1/2000 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
10/24/2000 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
9/30/2025 |
9/30/2028 |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
9/30/2025 |
9/30/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging OPW Site Sentinel Integra 100 |
9/30/2025 |
9/30/2026 |
|
Leak Detect - Tank
|
Hydrostatic Reservoir Interstitial Monitoring Sensors |
9/30/2025 |
9/30/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
8/23/2024 |
8/23/2027 |
|
Piping
|
Fiberglass Double Wall Ameron |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
8/23/2024 |
8/23/2027 |
Leak Detect - Piping
|
Sump Sensor |
8/23/2024 |
8/23/2027 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
8/23/2024 |
8/23/2027 |
|
Tank
|
Fiberglass Brine Filled Double Wall XERXES |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Double Wall Ameron
|
Precision Test (Piping)
|
Pass
|
7/28/2021
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
Dispenser Information
Name\ID 1/2
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
8/23/2024
|
8/23/2027
|
Leak Detect - Piping
|
Sump Sensor |
9/30/2025
|
9/30/2026
|
Name\ID 3/4
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
8/23/2024
|
8/23/2027
|
Leak Detect - Piping
|
Sump Sensor |
9/30/2025
|
9/30/2026
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found