Notice of Violations (Current)
NOV Number:
E0020261657
(Pending)
Issue Date:
6/29/2026
Expiration Date:
8/28/2026
View NOV Form
| Tanks |
Violations |
| 2 |
Miscellaneous - Equipment in disrepair 176.410 (Fill Adaptor) |
| 2 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
NOV Number:
E0020261658
(Pending)
Issue Date:
6/29/2026
Expiration Date:
8/28/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers. Reference 175.210 h) |
| Facility |
Fire Extinguishers - Past due for annual testing - Fire extinguishers require annual testing. Have annual testing performed and tag all fire extinguishers accordingly. (Last pass May 2024) |
IEMA Numbers Associated with the Facility
No IEMA Numbers Found
LUST
Fund Eligibility and Deductibility Determinations
No Applications Found
Tank Number 1
| Capacity: |
8000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Premium |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
8/23/2000 |
|
Abandoned Material: |
|
| Current Age: |
26 |
|
Abandoned Date: |
|
| Install Date: |
4/19/2000 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
7/20/2000 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
2/12/2026 |
2/12/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD |
2/12/2026 |
2/12/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
12/11/2025 |
12/11/2028 |
|
Piping
|
Fiberglass Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
12/11/2025 |
12/11/2028 |
|
Spill Contain Device
|
Double Wall Spill Bucket |
12/11/2025 |
12/11/2028 |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Single Wall Piping
|
Precision Test (Piping)
|
Pass
|
2/12/2026
|
|
Piping
|
Fiberglass Single Wall Piping A.O. Smith
|
Precision Test (Piping)
|
Pass
|
2/12/2026
|
|
Tank
|
Fiberglass Single Wall
|
Precision Test (Tank)
|
Pass
|
11/16/2025
|
Tank Number 2
| Capacity: |
12000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
8/23/2000 |
|
Abandoned Material: |
|
| Current Age: |
26 |
|
Abandoned Date: |
|
| Install Date: |
4/19/2000 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
7/20/2000 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
2/12/2026 |
2/12/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD |
2/12/2026 |
2/12/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
12/11/2025 |
12/11/2028 |
|
Piping
|
Fiberglass Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Not Installed STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Double Wall Spill Bucket |
12/11/2025 |
12/11/2028 |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Single Wall Piping
|
Precision Test (Piping)
|
Pass
|
2/12/2026
|
|
Tank
|
Fiberglass Single Wall
|
Precision Test (Tank)
|
Pass
|
5/22/2024
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
Dispenser Information
Name\ID 1/2
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Not Installed UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Name\ID 3/4
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Not Installed UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Name\ID 5/6
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Not Installed UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found