| 1, 2, 3 |
Dispensers - hoses cracked, split or worn and require replacement - Dispenser 1 main hose is worn. |
| 1 |
Install or replace lockable fill pipe caps. |
| 1, 2, 3 |
Triennial spill prevention equipment testing not completed. |
| 1, 2, 3 |
Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - STP Containment sumps require testing. |
| 1 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - STP sump(s) contain(s) liquid. Remove liquid and repair containment to prevent further liquid ingress. Must show documentaion showing repairs completed. (Per 41 Ill Admin code 175.410(h))
L3: (Reg STP) Fuel Alarm. |