Notice of Violatlions (Current)
NOV Number:
E0020260266
(Pending)
Issue Date:
2/3/2026
Expiration Date:
4/4/2026
View NOV Form
| Tanks |
Violations |
| 1, 2 |
Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - T1 Regular vapor bucket lid is not secured. The ring is missing. Repair lid support so lid is secured. T2 Premium STP sump lid is cracked. Replace STP sump lid. |
| 1, 2 |
Dispensers - hoses cracked, split or worn and require replacement - Replace main hoses |
| 1, 2, 3, 4 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - 175.405 a) 1) A) Spill containment equipment that will prevent release of product to
the environment when the transfer hose is detached from the fill
pipe (e.g., a spill catch basin). Spill containment equipment shall
be maintained in a dry, clean state. |
NOV Number:
E0020260267
(Pending)
Issue Date:
2/3/2026
Expiration Date:
4/4/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Code complying instruction/warning signs are not properly mounted at each dispenser island - Warning signs shall be visible from all dispensers. 175.220 a) Minimum signage requires letters shall not be less than 7/8” in height. The top of the sign shall be mounted no higher than 10’ above grade. The wording shall include a minimum of 1) “Warning” 2) “Stop Engine” 3) “No Smoking” 4) “Persons fueling vehicles shall remain with their vehicle, at the nozzle, while fueling is in progress” 5) “It is unlawful and dangerous for anyone to dispense gasoline into unapproved containers” |