Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2038282
Status: Active
Facility Name: Roseland Community Hospital
Address: 45 West 111th Street Chicago, IL 60628
County: Cook
Property Parcel:
Facility Type: Hospital
Owner Type: Private
Green Tag Decal: Z003961
Green Tag Issue Date: 7/18/2024
Green Tag Expiration Date: 12/31/2026

Owner Details

Owner Name: Roseland Community Hospital
Owner Address: 45 West 111th Street Chicago, IL 60628
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 7/18/2025

Motor Fuel Dispensing Permits

No MFD Permits Found

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0028039 Roseland Community Hospital Current Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020251761 (Pending)    Issue Date: 7/10/2025    Expiration Date: 9/8/2025    View NOV Form

Tanks Violations
1 Annual leak detection certification not completed (Required annually). - Failed Test on 7/01/2025. Probe is not reading. Repair and Retest.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 6000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/19/1998 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Cathodic Protection 5/31/2024 5/31/2027
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping European with No Test Req Suction N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 4B 5/22/2024 5/22/2025
Overfill Prev Device Overfill Drop Tube Valve 2/8/2023 2/8/2026
Piping Steel Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 11/18/2022 11/18/2025
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Piping American with Annual Prec Line Testing Suction Functional Pass 11/18/2022
Piping Steel Single Wall Piping Precision Test (Piping) Pass 7/1/2025
Tank Fiberglass Single Wall Precision Test (Tank) Pass 7/1/2025

Dispenser Information



MFD Motorfuel Dispensing Forms

No Forms Found