Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2036561
Status: Active
Facility Name: 7-Eleven #32334
Address: 2130 West Galena Blvd. Aurora, IL 60506
County: Kane
Property Parcel: 15-19-256-018
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y002754
Green Tag Issue Date: 3/22/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: 7-Eleven, Inc.
Owner Address: 3200 Hackberry Road - Gas Compliance Irving, TX 75063
Owner Status: Current Owner
Purchase Date: 1/1/1998
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 12/13/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 3/22/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0014207 7-Eleven, Inc. Current Owner 1/1/1998
U0023040 7-Eleven, Inc./DO NOT USE # Former Owner
U0020425 The Southland Corporation Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020252765 (Pending)    Issue Date: 10/20/2025    Expiration Date: 12/19/2025    View NOV Form

Tanks Violations
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - 175.210 h)The attendant shall at all times be able to communicate with persons in the dispensing area. Repair or replace intercom.

NOV Number: E0020252774 (Pending)    Issue Date: 10/20/2025    Expiration Date: 12/19/2025    View NOV Form

Tanks Violations
1, 2 Dispensers - hoses cracked, split or worn and require replacement - The main hose has a tear in it. Replace
Facility Miscellaneous - The emergency shut off switch at the control station is blocked and needs a sign. Either remove product display or relocate the shut off switch. A sign will be required also. 175.210 d) 3) Equipped with an emergency stop at all control stations, which shall be conspicuously marked and readily accessible to the attendant, whether or not the control station is less than 20 feet from any dispenser or a security booth is provided for the attendant. The emergency stop shall be located in a position to allow all dispensing devices to be readily visible to the attendant, or as approved by OSFM. Each emergency stop shall be identified by a sign on all-weather materials stating "EMERGENCY STOP" in 2 inch red capital letters.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 15000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/28/1998 Abandoned Material:
Current Age: 27 Abandoned Date:
Install Date: 7/1/1998 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/28/1998

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Jacketed Steel Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 9/26/2025 9/26/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 9/26/2025 9/26/2026
Overfill Prev Device Overfill Drop Tube Valve 9/26/2025 9/26/2028
Piping Flexible Double Wall Total Containment Enviroflex non-corrosive N/A N/A
Piping Single Wall STP/Tanktop Sump 10/30/2023 10/30/2026
Leak Detect - Piping Sump Sensor 9/26/2025 9/26/2026
Spill Contain Device Double Wall Spill Bucket 9/26/2025 9/26/2028
Tank Jacketed Steel Double Wall Total Containment N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/28/1998 Abandoned Material:
Current Age: 27 Abandoned Date:
Install Date: 7/1/1998 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/28/1998

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Jacketed Steel Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 9/26/2025 9/26/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 9/26/2025 9/26/2026
Overfill Prev Device Overfill Drop Tube Valve 9/26/2025 9/26/2028
Piping Flexible Double Wall Total Containment Enviroflex non-corrosive N/A N/A
Piping Single Wall STP/Tanktop Sump 10/30/2023 10/30/2026
Leak Detect - Piping Sump Sensor 9/26/2025 9/26/2026
Spill Contain Device Double Wall Spill Bucket 9/26/2025 9/26/2028
Tank Jacketed Steel Double Wall Total Containment N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 10000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/28/1998 Abandoned Material:
Current Age: 27 Abandoned Date:
Install Date: 7/1/1998 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/28/1998

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Jacketed Steel Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 9/26/2025 9/26/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 9/26/2025 9/26/2026
Overfill Prev Device Overfill Drop Tube Valve 9/26/2025 9/26/2028
Piping Flexible Double Wall Total Containment Enviroflex non-corrosive N/A N/A
Piping Single Wall STP/Tanktop Sump 10/30/2023 10/30/2026
Leak Detect - Piping Sump Sensor 9/26/2025 9/26/2026
Spill Contain Device Double Wall Spill Bucket 9/26/2025 9/26/2028
Tank Jacketed Steel Double Wall Total Containment N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/30/2023 10/30/2026
Leak Detect - Piping Sump Sensor with positive shutdown 9/26/2025 9/26/2026



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/30/2023 10/30/2026
Leak Detect - Piping Sump Sensor with positive shutdown 9/26/2025 9/26/2026



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/30/2023 10/30/2026
Leak Detect - Piping Sump Sensor with positive shutdown 9/26/2025 9/26/2026



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/30/2023 10/30/2026
Leak Detect - Piping Sump Sensor with positive shutdown 9/26/2025 9/26/2026



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/30/2023 10/30/2026
Leak Detect - Piping Sump Sensor with positive shutdown 9/26/2025 9/26/2026

MFD Motorfuel Dispensing Forms

No Forms Found