Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2036503
Status: Active
Facility Name: Circle K #6712
Address: 1421 North Bridge Street Yorkville, IL 60560
County: Kendall
Property Parcel: 02-28-104-025
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z000186
Green Tag Issue Date: 9/5/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: RDK Ventures LLC
Owner Address: 1120 W. Warner Rd. Tempe, AZ 85284
Owner Status: Current Owner
Purchase Date: 1/7/2010
Type of Financial Responsibility: Guarantee
Financial Responsibility Reporting Due Date: 10/27/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0035671 RDK Ventures LLC Current Owner 1/7/2010
U0031151 Shell Oil Products US c/o Gilbarco Veeder-Root Former Owner
U0027449 Equilon Enterprises, LLC Former Owner
U0013849 Shell Oil Products Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020261360 (Pending)    Issue Date: 5/26/2026    Expiration Date: 7/25/2026   

Tanks Violations
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - 175.210 h)The attendant shall at all times be able to communicate with persons in the dispensing area. Repair or replace intercom.

NOV Number: E0020261361 (Pending)    Issue Date: 5/26/2026    Expiration Date: 7/25/2026   

Tanks Violations
1, 2 Dispensers - hoses cracked, split or worn and require replacement - Replace main hoses.
Facility Facility Operation and Maintenance Plan not completed or available. - Operations and Maintenance Template needs to be updated and kept on site. https://sfm.illinois.gov/
Facility Missing copy of emergency instructions or emergency procedures plan - Emergency Procedures Plan needs to be updated and kept on site. https://sfm.illinois.gov/
1, 2 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - 175.405 a) 1) A) Spill containment equipment that will prevent release of product to the environment when the transfer hose is detached from the fill pipe (e.g., a spill catch basin). Spill containment equipment shall be maintained in a dry, clean state.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/23/2000 Abandoned Material:
Current Age: 25 Abandoned Date:
Install Date: 7/12/2000 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/13/2000

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/30/2026 3/30/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 3/30/2026 3/30/2027
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 3/30/2026 3/30/2027
Overfill Prev Device Overfill Drop Tube Valve 4/22/2024 4/22/2027
Piping Fiberglass Double Wall Ameron N/A N/A
Piping Single Wall STP/Tanktop Sump 3/6/2025 3/6/2028
Leak Detect - Piping Sump Sensor 3/30/2026 3/30/2027
Spill Contain Device Double Wall Spill Bucket 4/22/2024 4/22/2027
Tank Fiberglass Double Wall Fluid Containment Brine Filled N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Precision Test (Piping) Pass 3/30/2026
Tank Fiberglass Double Wall Fluid Containment Brine Filled Precision Test (Tank) Pass 5/23/2024



Tank Number 2

Capacity: 12000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/23/2000 Abandoned Material:
Current Age: 25 Abandoned Date:
Install Date: 7/12/2000 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/13/2000

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/30/2026 3/30/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 3/30/2026 3/30/2027
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 3/30/2026 3/30/2027
Overfill Prev Device Overfill Drop Tube Valve 4/22/2024 4/22/2027
Piping Fiberglass Double Wall Ameron N/A N/A
Piping Single Wall STP/Tanktop Sump 3/6/2025 3/6/2028
Leak Detect - Piping Sump Sensor 3/30/2026 3/30/2027
Spill Contain Device Double Wall Spill Bucket 4/22/2024 4/22/2027
Tank Fiberglass Double Wall Fluid Containment Brine Filled N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Precision Test (Piping) Pass 3/30/2026
Tank Fiberglass Double Wall Fluid Containment Brine Filled Precision Test (Tank) Pass 5/23/2024

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/25/2025 6/25/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/30/2026 3/30/2027



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/25/2025 6/25/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/30/2026 3/30/2027



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 3/6/2025 3/6/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/30/2026 3/30/2027



Name\ID 15/16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 3/6/2025 3/6/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/30/2026 3/30/2027



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/25/2025 6/25/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/30/2026 3/30/2027



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 3/6/2025 3/6/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/30/2026 3/30/2027



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 3/6/2025 3/6/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/30/2026 3/30/2027



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/25/2025 6/25/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/30/2026 3/30/2027

MFD Motorfuel Dispensing Forms