Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2036254
Status: Active
Facility Name: CarMax #7146
Address: 101 North Wolf Road Hillside, IL 60162
County: Cook
Property Parcel:
Facility Type: Auto Dealer
Owner Type: Private
Green Tag Decal: AA00345
Green Tag Issue Date: 6/5/2025
Green Tag Expiration Date: 12/31/2027

Owner Details

Owner Name: CarMax Auto Superstores, Inc.
Owner Address: 12800 Tuckahoe Creek Parkway Richmond, VA 23238
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 1/5/2027

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Fleet 6/5/2025 12/31/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0026349 CarMax Auto Superstores, Inc. Current Owner
U0026448 Carmax Former Owner 5/1/1998

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020253221 (Pending)    Issue Date: 12/8/2025    Expiration Date: 2/6/2026    View NOV Form

Tanks Violations
1 Tank monitor does not appear to function properly and requires maintenance. - FAILED TESTING BY TANKNOLOGY ON 9-23-2025 (VERIFY SYSTEM CONFIGURATION ) FAILED

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/26/1998 Abandoned Material:
Current Age: 27 Abandoned Date:
Install Date: 2/26/1998 Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date: 2/26/1998

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 9/23/2025 9/23/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300c 10/21/2024 9/23/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 9/23/2025 9/23/2026
Overfill Prev Device Overfill Alarm 10/21/2025 10/21/2028
Overfill Prev Device Overfill Drop Tube Valve 10/21/2024 10/21/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 6/18/2025 6/18/2028
Leak Detect - Piping Stand Alone Sump Sensor Franklin Fueling Systems DC 404 stand alone sump sensor 1/7/2022 1/7/2023
Leak Detect - Piping Sump Sensor 9/23/2025 9/23/2026
Spill Contain Device Double Wall Spill Bucket 11/15/2023 11/15/2026
Tank Fiberglass Double Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 8/1/2019
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 9/23/2025

Dispenser Information



Name\ID 1

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/18/2025 6/18/2028
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID gas

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/18/2025 6/18/2028
Leak Detect - Piping Stand Alone Sump Sensor Franklin Fueling Systems DC 404 stand alone sump sensor 9/23/2025 9/23/2026

MFD Motorfuel Dispensing Forms

No Forms Found