Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2035960
Status: Active
Facility Name: Circle K #6704
Address: 1000 Milwaukee Avenue Lincolnshire, IL 60069
County: Lake
Property Parcel: 15-27-203-005
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z000817
Green Tag Issue Date: 8/15/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: RDK Ventures LLC
Owner Address: 1120 W. Warner Rd. Tempe, AZ 85284
Owner Status: Current Owner
Purchase Date: 1/7/2010
Type of Financial Responsibility: Guarantee
Financial Responsibility Reporting Due Date: 10/27/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0035671 RDK Ventures LLC Current Owner 1/7/2010
U0031151 Shell Oil Products US c/o Gilbarco Veeder-Root Former Owner
U0027449 Equilon Enterprises, LLC Former Owner
U0013849 Shell Oil Products Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020261049 (Pending)    Issue Date: 4/20/2026    Expiration Date: 6/19/2026    View NOV Form

Tanks Violations
1, 2 Water in dispenser containment with interstitial sensors - Remove water and repair containments to prevent water ingress - Dispenser 15/16 containment sump(s) contain(s) 29" liquid (up to shear valve). Remove liquid and repair containment to prevent further liquid ingress. Must provide documentation showing repairs completed. (Per 41 Ill Admin code 175.410(h))

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/14/2000 Abandoned Material:
Current Age: 26 Abandoned Date:
Install Date: 10/22/1999 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 2/24/2000

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 10/30/2025 10/30/2026
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors with monitor 10/30/2025 10/30/2026
Overfill Prev Device Overfill Drop Tube Valve 2/16/2026 2/16/2029
Piping Fiberglass Single Wall Piping Ameron N/A N/A
Piping Single Wall STP/Tanktop Sump 4/18/2024 4/18/2027
Leak Detect - Piping Sump Sensor 12/11/2023 12/11/2024
Leak Detect - Piping Piping Sump Sensors Not Regulated N/A N/A
Spill Contain Device Double Wall Spill Bucket 1/6/2026 1/6/2029
Tank Fiberglass Brine Filled Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Ameron Precision Test (Piping) Pass 10/30/2025



Tank Number 2

Capacity: 15000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/14/2000 Abandoned Material:
Current Age: 26 Abandoned Date:
Install Date: 10/22/1999 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 2/24/2000

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 10/30/2025 10/30/2026
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors with monitor 10/30/2025 10/30/2026
Overfill Prev Device Overfill Drop Tube Valve 2/16/2026 2/16/2029
Piping Fiberglass Single Wall Piping Ameron N/A N/A
Piping Single Wall STP/Tanktop Sump 4/18/2024 4/18/2027
Leak Detect - Piping Sump Sensor 12/11/2023 12/11/2024
Leak Detect - Piping Piping Sump Sensors Not Regulated N/A N/A
Spill Contain Device Double Wall Spill Bucket 1/6/2026 1/6/2029
Tank Fiberglass Brine Filled Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Ameron Precision Test (Piping) Pass 10/30/2025

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/16/2024 9/16/2027
Leak Detect - Piping Piping Sump Sensors Not Regulated N/A N/A



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/16/2024 9/16/2027
Leak Detect - Piping Piping Sump Sensors Not Regulated N/A N/A



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/16/2024 9/16/2027
Leak Detect - Piping Piping Sump Sensors Not Regulated N/A N/A



Name\ID 15/16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/16/2024 9/16/2027
Leak Detect - Piping Piping Sump Sensors Not Regulated N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/16/2024 9/16/2027
Leak Detect - Piping Piping Sump Sensors Not Regulated N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/16/2024 9/16/2027
Leak Detect - Piping Piping Sump Sensors Not Regulated N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/16/2024 9/16/2027
Leak Detect - Piping Piping Sump Sensors Not Regulated N/A N/A



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/16/2024 9/16/2027
Leak Detect - Piping Piping Sump Sensors Not Regulated N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found