Notice of Violations (Current)
NOV Number:
E0020262083
(Pending)
Issue Date:
8/18/2026
Expiration Date:
10/17/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - I can see a intercom system, but it's blocked by display racks. I don't know if it is functional.
175.210 h)The attendant shall at all times be able to communicate with persons in the dispensing area. Repair or replace intercom. |
| Facility |
Miscellaneous - Control station does not have a readily accessible emergency shut off switch. A sign is required also as stated in the remarks. |
NOV Number:
E0020262084
(Pending)
Issue Date:
8/18/2026
Expiration Date:
10/17/2026
View NOV Form
| Tanks |
Violations |
| 1, 3 |
Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - The regular and diesel probe well steel lids are not secured. The steel frame comes up from the concrete. The lid supporting brackets and lids need to be secured. |
| 1, 2 |
Dispensers - hoses cracked, split or worn and require replacement - Replace main hose it is kinked. |
| 1, 2, 3 |
Line interstitial sensors have been raised and rendered inoperational. - Dispenser sumps 5/6, 9/10, and STP sumps T1 regular and T3 diesel have raised sensors.
Section 175.640 a)2) All new and existing sump sensors must be installed so as to detect liquid
per manufacturer's specifications or, if not specified by the manufacturer, at the lowest point in the sump. |
| 2 |
Miscellaneous - Tank annular sensor wire is open into the tank interstice. |
| 1, 2, 3 |
Piping interstitial must be open in all sumps - Check all UDC and STP sumps to make sure interstice is able to drain into sumps. |
IEMA Numbers Associated with the Facility
No IEMA Numbers Found
LUST
Fund Eligibility and Deductibility Determinations
No Applications Found
Tank Number 1
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
11/18/1997 |
|
Abandoned Material: |
|
| Current Age: |
29 |
|
Abandoned Date: |
|
| Install Date: |
8/1/1997 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
8/25/1997 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Jacketed Steel Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
5/26/2026 |
5/26/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350R with CSLD |
5/26/2026 |
5/26/2027 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
5/26/2026 |
5/26/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
5/26/2026 |
5/26/2029 |
|
Piping
|
Flexible Double Wall OPW Pisces |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
12/18/2025 |
12/18/2028 |
Leak Detect - Piping
|
Sump Sensor |
12/18/2025 |
12/18/2028 |
|
Spill Contain Device
|
Double Wall Spill Bucket |
5/26/2026 |
5/26/2029 |
|
Tank
|
Jacketed Steel Double Wall Total Containment |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Tank
|
Jacketed Steel Double Wall Total Containment
|
Precision Test (Tank)
|
Pass
|
10/29/2019
|
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors
|
Sensor Functional
|
Pass
|
3/18/2010
|
|
Leak Detect - Piping
|
Non-Discriminating Sump Sensor
|
Sensor Functional
|
Pass
|
3/18/2010
|
Tank Number 2
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Premium |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
11/18/1997 |
|
Abandoned Material: |
|
| Current Age: |
29 |
|
Abandoned Date: |
|
| Install Date: |
8/1/1997 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
8/25/1997 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Jacketed Steel Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
5/26/2026 |
5/26/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350R with CSLD |
5/26/2026 |
5/26/2027 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
5/26/2026 |
5/26/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
5/26/2026 |
5/26/2029 |
|
Piping
|
Flexible Double Wall OPW Pisces |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
12/18/2025 |
12/18/2028 |
Leak Detect - Piping
|
Sump Sensor |
12/18/2025 |
12/18/2028 |
|
Spill Contain Device
|
Double Wall Spill Bucket |
5/26/2026 |
5/26/2029 |
|
Tank
|
Jacketed Steel Double Wall Total Containment |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Tank
|
Jacketed Steel Double Wall Total Containment
|
Precision Test (Tank)
|
Pass
|
10/2/2019
|
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors
|
Sensor Functional
|
Pass
|
3/18/2010
|
|
Leak Detect - Piping
|
Non-Discriminating Sump Sensor
|
Sensor Functional
|
Pass
|
3/18/2010
|
Tank Number 3
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
11/18/1997 |
|
Abandoned Material: |
|
| Current Age: |
29 |
|
Abandoned Date: |
|
| Install Date: |
8/1/1997 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
8/25/1997 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Jacketed Steel Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
5/26/2026 |
5/26/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350R with CSLD |
5/26/2026 |
5/26/2027 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
5/26/2026 |
5/26/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
5/26/2026 |
5/26/2029 |
|
Piping
|
Flexible Double Wall OPW Pisces |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
12/18/2025 |
12/18/2028 |
Leak Detect - Piping
|
Sump Sensor |
12/18/2025 |
12/18/2028 |
|
Spill Contain Device
|
Double Wall Spill Bucket |
5/26/2026 |
5/26/2029 |
|
Tank
|
Jacketed Steel Double Wall Total Containment |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors
|
Sensor Functional
|
Pass
|
3/18/2010
|
|
Leak Detect - Piping
|
Non-Discriminating Sump Sensor
|
Sensor Functional
|
Pass
|
3/18/2010
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found