Notice of Violations (Current)
NOV Number:
E0020262083
(Referred to Legal)
Issue Date:
8/18/2026
Expiration Date:
10/17/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Miscellaneous - Control station does not have a readily accessible emergency shut off switch. A sign is required also as stated in the remarks. |
NOV Number:
E0020262084
(Referred to Legal)
Issue Date:
8/18/2026
Expiration Date:
10/17/2026
View NOV Form
| Tanks |
Violations |
| 1, 3 |
Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - The regular and diesel probe well steel lids are not secured. The steel frame comes up from the concrete. The lid supporting brackets and lids need to be secured. |
| 2 |
Miscellaneous - Tank annular sensor wire is open into the tank interstice. |
| 1, 2, 3 |
Piping interstitial must be open in all sumps - Check all UDC and STP sumps to make sure interstice is able to drain into sumps. |