Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2035001
Status: Active
Facility Name: Roselle Real Estate Inc.
Address: 1330 West Lake Street Roselle, IL 60172
County: Du Page
Property Parcel: 02-08-213-005
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z000122
Green Tag Issue Date: 4/30/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: Roselle Real Estate Inc.
Owner Address: 1330 West Lake Street Roselle, IL 60172
Owner Status: Current Owner
Purchase Date: 11/20/2025
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 6/10/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0041829 Roselle Real Estate Inc. Current Owner 11/20/2025
U0039521 Thorntons, LLC Former Owner 2/11/2019
U0014995 Thornton's, Inc. - DO NOT USE THIS OWNER ID Former Owner 9/17/1996

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020261305 (Pending)    Issue Date: 5/18/2026    Expiration Date: 7/17/2026    View NOV Form

Tanks Violations
1, 2, 3, 4, 5 Annual electronic line leak detector test not completed. - Line leak detectors need annual testing. Testing shall be performed and passing results entered on OSFM portal.
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - Emergency shut off switch needs annual testing performed. OSFM form shall be kept on site.
1, 2, 3, 4, 5 Annual leak detection certification not completed (Required annually). - Annual leak detection testing shall be performed and passing results entered on OSFM portal.
1, 2, 3, 4, 5 Document that emergency shut-off (shear valves) are in proper working order - Shear valves need annual testing performed. OSFM form shall be completed and kept on site.
Facility Facility Operation and Maintenance Plan not completed or available. - Operations and Maintenance Template needs to be updated and kept on site. https://sfm.illinois.gov/
Facility Financial responsibility must be reported yearly - Section 176.240 Recordkeeping a) Owners or operators shall maintain evidence of all financial responsibility mechanisms used to demonstrate financial responsibility (pursuant to this Subpart) for a UST until released from the requirements of this Subpart under Section 176.245. An owner or operator shall maintain that evidence at the UST site or the owner's or operator's principal place of business. Records maintained off-site shall be made available upon written or oral request from OSFM. b)3) An owner or operator using a commercial or private insurance policy or risk retention group coverage shall maintain a copy of the signed insurance policy or risk retention group coverage policy, with the endorsement or certificate of insurance and any amendments to the agreement.
5 Line interstitial sensor functional test not accomplished (Required annually). - STP and UDC sump sensors need annual testing performed. Passing results shall be entered on OSFM portal.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual walkthrough needs to be performed. OSFM form shall be completed and kept on site.
Facility Missing copy of emergency instructions or emergency procedures plan - Emergency Procedures Plan needs to be updated and kept on site. https://sfm.illinois.gov/
Facility Missing list of designated Class A/B & C Operators
1 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - 175.405 a) 1) A) Spill containment equipment that will prevent release of product to the environment when the transfer hose is detached from the fill pipe (e.g., a spill catch basin). Spill containment equipment shall be maintained in a dry, clean state.
Facility Submit Notification Form For Ownership Address Change - The Notification Form is available at: https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. This form is required to be submitted within 30 days of an ownership change.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
18-0083 1/22/2018 Emergency Response

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 12000 Gasoline - Regular Currently in use Federal $0.00
2 12000 Gasoline - Premium Currently in use Federal $0.00
3 12000 Diesel Fuel Currently in use Federal $0.00
4 6000 Diesel Fuel Currently in use Federal $0.00
5 6000 Diesel Fuel Currently in use Federal $0.00


Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active
9/10 Active
11/12 Active
13/14 Active
15/16 Active


MFD Motorfuel Dispensing Forms