Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2034978
Status: Active
Facility Name: Amoco 13407
Address: 8800 W. Grand Ave. River Grove, IL 60171
County: Cook
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y001455
Green Tag Issue Date: 3/2/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: RNG Fuels, Inc.
Owner Address: 8800 W. Grand Ave. River Grove, IL 60171
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Certificate of Deposit
Financial Responsibility Reporting Due Date: 12/3/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 1/6/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0037222 RNG Fuels, Inc. Current Owner
U0032360 Angel Associates, LP Former Owner 12/18/2009
U0027493 Amoco Oil Company Former Owner 7/1/1996
U0000552 BP Products North America, Inc. Former Owner 7/1/1996

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
00742-2025UPG Upgrade Approved / Issued 6/16/2025 6/16/2025 12/16/2025 Documents

Notice of Violatlions (Current)

NOV Number: E0020251404 (Pending)    Issue Date: 6/2/2025    Expiration Date: 8/1/2025    View NOV Form

Tanks Violations
1, 2, 3 Line leak detection equipment in alarm or failed test, must repair or replace. - ATG showing all 3 sump sensors in alarm
1, 2, 3 Tank interstitial sensors in alarm or failed test, must repair or replace. - Contractor performed work and veeder root print out showed normal sensors at time of work completed. At time of reinspect RUL and Diesel tank top sumps had water in them and sensor was in alarm. Veeder root also showed Diesel interstitial sensor in alar
1, 2, 3 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Provide documentation of repairs made

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/10/1996 Abandoned Material:
Current Age: 29 Abandoned Date:
Install Date: 7/24/1996 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/24/1996

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 6/17/2025 6/17/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root EMC with CSLD 6/18/2025 6/18/2026
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 6/18/2025 6/18/2026
Overfill Prev Device Overfill Drop Tube Valve 6/11/2024 6/11/2027
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 6/11/2024 6/11/2027
Leak Detect - Piping Non-Discriminating Sump Sensor 8/19/2020 6/28/2021
Leak Detect - Piping Sump Sensor 6/18/2025 6/18/2026
Spill Contain Device Single Wall Spill Bucket 6/11/2024 6/11/2027
Tank Fiberglass Double Wall Containment Solutions N/A N/A
Tank Fiberglass Brine Filled Double Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 6/11/2024



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/10/1996 Abandoned Material:
Current Age: 29 Abandoned Date:
Install Date: 7/24/1996 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/24/1996

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 6/18/2025 6/18/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root EMC with CSLD 6/18/2025 6/18/2026
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 6/17/2025 6/17/2026
Overfill Prev Device Overfill Drop Tube Valve 6/11/2024 6/11/2027
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 6/11/2024 6/11/2027
Leak Detect - Piping Sump Sensor 6/11/2024 6/11/2025
Spill Contain Device Single Wall Spill Bucket 6/11/2024 6/11/2027
Tank Fiberglass Double Wall Containment Solutions N/A N/A
Tank Fiberglass Brine Filled Double Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 6/11/2024



Tank Number 3

Capacity: 10000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/10/1996 Abandoned Material:
Current Age: 29 Abandoned Date:
Install Date: 7/24/1996 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/24/1996

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 6/18/2025 6/18/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root EMC with CSLD 6/18/2025 6/18/2026
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 6/18/2025 6/18/2026
Overfill Prev Device Overfill Drop Tube Valve 6/11/2024 6/11/2027
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 6/11/2024 6/11/2027
Leak Detect - Piping Non-Discriminating Sump Sensor 8/19/2020 8/19/2021
Leak Detect - Piping Sump Sensor 6/18/2025 6/18/2026
Spill Contain Device Single Wall Spill Bucket 6/11/2024 6/11/2027
Tank Fiberglass Double Wall Containment Solutions N/A N/A
Tank Fiberglass Brine Filled Double Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 6/11/2024

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/11/2024 6/11/2027
Leak Detect - Piping Sump Sensor 6/18/2025 6/18/2026



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/11/2024 6/11/2027
Leak Detect - Piping Sump Sensor 6/18/2025 6/18/2026



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/11/2024 6/11/2027
Leak Detect - Piping Sump Sensor 6/18/2025 6/18/2026



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/11/2024 6/11/2027
Leak Detect - Piping Sump Sensor 6/18/2025 6/18/2026

MFD Motorfuel Dispensing Forms