Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2034799
Status: Active
Facility Name: Pride of Saint Charles
Address: 1505 Lincoln Highway St. Charles, IL 60174
County: Kane
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: AA01250
Green Tag Issue Date: 6/18/2025
Green Tag Expire Date: 12/31/2027
MFD Type: Self Service

Owner Details

Owner Name: CIMA Developers L.P.
Owner Address: 30W180 Butterfield Rd. Warrenville, IL 60555
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 5/4/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0038736 CIMA Developers L.P. Current Owner
U0032360 Angel Associates, LP Former Owner 12/18/2009
U0027493 Amoco Oil Company Former Owner
U0000552 BP Products North America, Inc. Former Owner

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
00070-2026UPG Upgrade Approved / Issued 1/19/2026 1/20/2026 7/21/2026 Documents

Notice of Violatlions (Current)

NOV Number: E0020261006 (Pending)    Issue Date: 4/15/2026    Expiration Date: 6/14/2026    View NOV Form

Tanks Violations
1, 2, 3 Line leak detection equipment in alarm or failed test, must repair or replace. - PER PROTANIC TEST 4/9/2026: Dispenser 9/10 sensor FAILS; there is a s5: "communication" alarm on arrival and departure. Dispenser 11/12 sensor FAILS; there is a s6: "communication" alarm and a "sensor fault" alarm on arrival and departure. REPAIR /REPLACE SENSORS, RETEST AND UPLOAD PASSING RESULTS TO OSFM WEBSITE.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/9/1996 Abandoned Material:
Current Age: 30 Abandoned Date:
Install Date: 5/3/1996 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/3/1996

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/9/2026 4/9/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 4/9/2026 4/9/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 4/9/2026 4/9/2027
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 6/18/2024 6/18/2027
Piping Fiberglass Double Wall A.O. Smith N/A N/A
Piping Single Wall STP/Tanktop Sump 4/23/2025 4/23/2028
Leak Detect - Piping Sump Sensor 4/9/2026 4/9/2027
Spill Contain Device Single Wall Spill Bucket 4/23/2025 4/23/2028
Tank Composite Double Wall Clawson N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall A.O. Smith Precision Test (Piping) Pass 1/26/2026



Tank Number 2

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/9/1996 Abandoned Material:
Current Age: 30 Abandoned Date:
Install Date: 5/3/1996 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/3/1996

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/9/2026 4/9/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 4/9/2026 4/9/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 4/9/2026 4/9/2027
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 6/18/2024 6/18/2027
Piping Fiberglass Double Wall A.O. Smith N/A N/A
Piping Single Wall STP/Tanktop Sump 4/23/2025 4/23/2028
Leak Detect - Piping Sump Sensor 4/9/2026 4/9/2027
Spill Contain Device Single Wall Spill Bucket 4/23/2025 4/23/2028
Tank Composite Double Wall Clawson N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall A.O. Smith Precision Test (Piping) Pass 1/26/2026



Tank Number 3

Capacity: 12000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/9/1996 Abandoned Material:
Current Age: 30 Abandoned Date:
Install Date: 5/3/1996 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/3/1996

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/9/2026 4/9/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 4/9/2026 4/9/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 4/9/2026 4/9/2027
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 6/18/2024 6/18/2027
Piping Fiberglass Double Wall A.O. Smith N/A N/A
Piping Single Wall STP/Tanktop Sump 4/23/2025 4/23/2028
Leak Detect - Piping Non-Discriminating Sump Sensor 6/23/2021 6/23/2022
Leak Detect - Piping Sump Sensor 4/9/2026 4/9/2027
Spill Contain Device Single Wall Spill Bucket 4/23/2025 4/23/2028
Tank Composite Double Wall Clawson N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/23/2025 4/23/2028
Leak Detect - Piping Sump Sensor with positive shutdown 5/13/2026 5/13/2027



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/23/2025 4/23/2028
Leak Detect - Piping Sump Sensor with positive shutdown 5/13/2026 5/13/2027



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/23/2025 4/23/2028
Leak Detect - Piping Sump Sensor with positive shutdown 4/9/2026 4/9/2027



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/23/2025 4/23/2028
Leak Detect - Piping Sump Sensor with positive shutdown 4/9/2026 4/9/2027



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/23/2025 4/23/2028
Leak Detect - Piping Sump Sensor with positive shutdown 4/9/2026 4/9/2027



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/23/2025 4/23/2028
Leak Detect - Piping Sump Sensor with positive shutdown 5/13/2026 5/13/2027

MFD Motorfuel Dispensing Forms

No Forms Found