Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2033910
Status: Active
Facility Name: T. H. Davidson & Company
Address: 10175 Vans Drive Frankfort, IL 60423
County: Will
Property Parcel:
Facility Type: Industrial / Manufacturing
Owner Type: Private
Green Tag Decal: Z004257
Green Tag Issue Date: 10/30/2024
Green Tag Expiration Date: 12/31/2026

Owner Details

Owner Name: T. H. Davidson & Company
Owner Address: 10175 Vans Drive Frankfort, IL 60423
Owner Status: Current Owner
Purchase Date: 1/1/2001
Type of Financial Responsibility: Letter of Credit
Financial Responsibility Reporting Due Date: 6/18/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Fleet 10/30/2024 12/31/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0035179 T. H. Davidson & Company Current Owner 1/1/2001
U0015651 Vans Material Company, Inc. Former Owner 5/5/1995

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020253022 (Pending)    Issue Date: 11/10/2025    Expiration Date: 1/9/2026    View NOV Form

Tanks Violations
1 Verify and test piping sump sensor for positive shutdown - Sump sensor failed test on 10/28/2025. Repair or replace.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/19/1995 Abandoned Material:
Current Age: 30 Abandoned Date:
Install Date: 4/3/1995 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 4/4/1995

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 10/28/2025 10/28/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 10/28/2025 10/28/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 10/28/2025 10/28/2026
Overfill Prev Device Overfill Drop Tube Valve 10/28/2025 10/28/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 9/7/2023 9/7/2026
Leak Detect - Piping Sump Sensor 7/3/2024 7/3/2025
Spill Contain Device Single Wall Spill Bucket 10/28/2025 10/28/2028
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 10/28/2025

Dispenser Information



Name\ID 1

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/7/2023 9/7/2026
Leak Detect - Piping Sump Sensor with positive shutdown 10/28/2025 10/28/2026

MFD Motorfuel Dispensing Forms

No Forms Found