Owner Summary
Click for Facility/Tank Ownership history
| Owner Number |
Owner Name |
Owner Status |
Purchase Date |
| U0039337 |
2513 Higgins LLC |
Current Owner |
12/1/2016 |
| U0022987 |
American Consolidated Transportation Co., Inc. |
Former Owner |
1/1/1979 |
Notice of Violations (Current)
NOV Number:
E0020250577
(Referred to Legal)
Issue Date:
3/5/2025
Expiration Date:
5/4/2025
View NOV Form
| Tanks |
Violations |
| 4, 5, 6, 7 |
Failed to Empty the Tank to 1" or Less - Per 175.810(a)(1), when placing tanks out of service, the tank and lines must be emptied immediately. The UST is considered empty when all materials have been removed to one inch or less. Upon my reinspection dated 10/18/24, I took a stick reading of each tank and all four tanks had more than an inch of product. These tanks have been out of service since 6/15/18! Please remove the product asap. |
| Facility |
Financial responsibility must be reported yearly - Per 41 Ill. Adm. Code 176.220, tank owners/operators must submit an electronic Financial Responsibility Report form on an annual basis. Financial Responsibility must be maintained until the tank is removed or properly abandoned in place by a licensed UST decommissiong contractor. The form can be found at: https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility. |
IEMA Numbers Associated with the Facility
| IEMA Number |
Inspection Date |
Inspection Type |
Permit Number |
| 17--0228 |
4/18/2017 |
Removal Log |
00335-2017REM |
| 17-0228 |
4/17/2017 |
Removal Log |
00335-2017REM |
LUST
Fund Eligibility and Deductibility Determinations
| IEMA Number |
Status |
OSFM Received Date |
OSFM Response Date |
Deductible |
Letter |
| 94-1757 |
Eligible |
6/19/1995
|
7/5/1995
|
$100,000
|
|
| 20170228 |
Eligible |
5/1/2017
|
5/1/2017
|
$5,000
|
Letter
|
Tank Number 1
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
4/17/2017 |
|
OSFM
First Notify Date: |
5/26/1994 |
|
Abandoned Material: |
|
| Current Age: |
38 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1979 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
2/1/2012 |
|
Fee Due: |
$0.00 |
| Product Date: |
1/1/1979 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Tank
|
Lining Materials Internal |
2/1/2012 |
2/1/2017 |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Leak Detect - Piping
|
Sump Sensor
|
Sensor Functional
|
Pass
|
5/13/2011
|
Tank Number 2
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
4/17/2017 |
|
OSFM
First Notify Date: |
5/26/1994 |
|
Abandoned Material: |
|
| Current Age: |
38 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1979 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
2/1/2012 |
|
Fee Due: |
$0.00 |
| Product Date: |
1/1/1979 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Tank
|
Lining Materials Internal |
2/1/2012 |
2/1/2017 |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Leak Detect - Piping
|
Sump Sensor
|
Sensor Functional
|
Pass
|
5/13/2011
|
Tank Number 3
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
4/18/2017 |
|
OSFM
First Notify Date: |
5/26/1994 |
|
Abandoned Material: |
|
| Current Age: |
38 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1979 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
5/12/2014 |
|
Fee Due: |
$0.00 |
| Product Date: |
1/1/1979 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Lining Materials Internal |
2/1/2012 |
2/1/2017 |
|
Leak Detect - Piping
|
European with No Test Req Suction |
Not applicable |
Not applicable |
|
Leak Detect - Tank
|
Automatic Tank Gauging OPW EECO 1500 |
No passing test found |
No passing test found |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
No passing test found |
No passing test found |
|
Piping
|
Fiberglass Single Wall Piping |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
No passing test found |
No passing test found |
|
Tank
|
Steel Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Leak Detect - Piping
|
Sump Sensor
|
Sensor Functional
|
Pass
|
5/13/2011
|
Tank Number 4
| Capacity: |
10000 |
|
Petroleum Use: |
None |
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Out of service |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
7/3/2002 |
|
Abandoned Material: |
|
| Current Age: |
24 |
|
Abandoned Date: |
|
| Install Date: |
3/27/2002 |
|
Red Tag Issue Date: |
10/1/2018 |
| Last Used Date: |
6/15/2018 |
|
Fee Due: |
$0.00 |
| Product Date: |
3/27/2002 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Composite Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
1/12/2016 |
1/12/2017 |
|
Leak Detect - Piping
|
Sump Sensor |
1/12/2016 |
1/12/2017 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Pneumercator TMS 3000 |
No passing test found |
No passing test found |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
1/12/2016 |
1/12/2017 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
No passing test found |
No passing test found |
|
Piping
|
Flexible Double Wall |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
No passing test found |
No passing test found |
|
Tank
|
Composite Double Wall Modern Welding Glasteel II |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Tank Number 5
| Capacity: |
3000 |
|
Petroleum Use: |
|
| Product: |
Motor Oil |
|
CERCLA Substance: |
|
| Status: |
Out of service |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
7/3/2002 |
|
Abandoned Material: |
|
| Current Age: |
24 |
|
Abandoned Date: |
|
| Install Date: |
3/27/2002 |
|
Red Tag Issue Date: |
10/1/2018 |
| Last Used Date: |
6/15/2018 |
|
Fee Due: |
$0.00 |
| Product Date: |
3/27/2002 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Composite Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
European with No Test Req Suction |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Sump Sensor |
1/12/2016 |
1/12/2017 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Pneumercator TMS 3000 |
No passing test found |
No passing test found |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
1/12/2016 |
1/12/2017 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
No passing test found |
No passing test found |
|
Piping
|
Flexible Double Wall |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
No passing test found |
No passing test found |
|
Tank
|
Composite Double Wall Modern Welding Glasteel II |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Tank Number 6
| Capacity: |
3000 |
|
Petroleum Use: |
|
| Product: |
Motor Oil |
|
CERCLA Substance: |
|
| Status: |
Out of service |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
7/3/2002 |
|
Abandoned Material: |
|
| Current Age: |
24 |
|
Abandoned Date: |
|
| Install Date: |
3/27/2002 |
|
Red Tag Issue Date: |
10/1/2018 |
| Last Used Date: |
6/15/2018 |
|
Fee Due: |
$0.00 |
| Product Date: |
3/27/2002 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Composite Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
European with No Test Req Suction |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Sump Sensor |
1/12/2016 |
1/12/2017 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Pneumercator TMS 3000 |
No passing test found |
No passing test found |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
1/12/2016 |
1/12/2017 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
No passing test found |
No passing test found |
|
Piping
|
Flexible Double Wall |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
No passing test found |
No passing test found |
|
Tank
|
Composite Double Wall Modern Welding Glasteel II |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Tank Number 7
| Capacity: |
3000 |
|
Petroleum Use: |
|
| Product: |
Used Oil |
|
CERCLA Substance: |
|
| Status: |
Out of service |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
7/3/2002 |
|
Abandoned Material: |
|
| Current Age: |
24 |
|
Abandoned Date: |
|
| Install Date: |
3/27/2002 |
|
Red Tag Issue Date: |
10/1/2018 |
| Last Used Date: |
6/15/2018 |
|
Fee Due: |
$0.00 |
| Product Date: |
3/27/2002 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Composite Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
European with No Test Req Suction |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Sump Sensor |
1/12/2016 |
1/12/2017 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Pneumercator TMS 3000 |
No passing test found |
No passing test found |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
1/12/2016 |
1/12/2017 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
No passing test found |
No passing test found |
|
Piping
|
Flexible Double Wall |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
No passing test found |
No passing test found |
|
Tank
|
Composite Double Wall Modern Welding Glasteel II |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
Dispenser Information
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found