Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2032941
Status: Active
Facility Name: Roosevelt & Kostner Amoco
Address: 4402 W. Roosevelt Rd. Chicago, IL 60624
County: Cook
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z002209
Green Tag Issue Date: 8/20/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: FKT Corp.
Owner Address: 4402 W. Roosevelt Rd. Chicago, IL 60624
Owner Status: Current Owner
Purchase Date: 6/1/2018
Type of Financial Responsibility: Designated Savings Account
Financial Responsibility Reporting Due Date: 2/9/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0039247 FKT Corp. Current Owner 6/1/2018
U0022665 Raybon, Lee Former Owner 1/1/1987

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020260928 (Pending)    Issue Date: 4/8/2026    Expiration Date: 6/7/2026    View NOV Form

Tanks Violations
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
1, 2, 3, 5 Annual leak detection certification not completed (Required annually).
1, 2, 3, 5 Annual line precision and mechanical line leak detector functional test not completed.
Facility Missing copies of Annual Walkthrough Inspection Report.
5 Precision tank test required. - No passing results for Kerosene for over 6 months
1, 2, 3, 5 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection).
1, 2, 3, 5 Tank monitor does not appear to function properly and requires maintenance. - Veeder Root only has In-tank testing results and there was a CSLD chip installed on this monitor and needs to be repaired, reprogrammed or replaced. Repair issues with Kerosene tank no passing results available. If need more product to pass then increase to passible level/

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
16-1140 1/13/2017 Abandonment Log 01586-2016ABN

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
20161141 Returned 4/18/2026 4/24/2026 $5,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/7/1994 Abandoned Material:
Current Age: 39 Abandoned Date:
Install Date: 1/1/1987 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1987

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Cathodic Protection 8/16/2024 8/16/2027
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 5/19/2026 5/19/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 5/19/2026 5/19/2027
Overfill Prev Device Overfill Drop Tube Valve 5/1/2024 5/1/2027
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Single Wall Spill Bucket 5/1/2024 5/1/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 5/19/2026



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/7/1994 Abandoned Material:
Current Age: 39 Abandoned Date:
Install Date: 1/1/1987 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1987

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Cathodic Protection 8/16/2024 8/16/2027
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 5/19/2026 5/19/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 5/19/2026 5/19/2027
Overfill Prev Device Overfill Drop Tube Valve 5/1/2024 5/1/2027
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Single Wall Spill Bucket 5/1/2024 5/1/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 5/19/2026
Piping Fiberglass Single Wall Piping Precision Test (Piping) Fail 5/1/2024



Tank Number 3

Capacity: 10000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/7/1994 Abandoned Material:
Current Age: 39 Abandoned Date:
Install Date: 1/1/1987 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1987

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Cathodic Protection 8/16/2024 8/16/2027
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 5/19/2026 5/19/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 5/19/2026 5/19/2027
Overfill Prev Device Overfill Drop Tube Valve 5/1/2024 5/1/2027
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Single Wall Spill Bucket 5/1/2024 5/1/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 5/19/2026



Tank Number 4

Capacity: 6000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Abandoned in place CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/7/1994 Abandoned Material: Inert material mixed with portland cement
Current Age: 39 Abandoned Date: 1/13/2017
Install Date: 1/1/1987 Red Tag Issue Date:
Last Used Date: 8/1/2009 Fee Due: $0.00
Product Date: 1/1/1987

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 2000 Petroleum Use: None
Product: Kerosene CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/7/1994 Abandoned Material:
Current Age: 39 Abandoned Date:
Install Date: 1/1/1987 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1987

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Cathodic Protection 8/16/2024 8/16/2027
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 5/19/2026 5/19/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 5/19/2026 5/19/2027
Overfill Prev Device Overfill Drop Tube Valve 5/1/2024 5/1/2027
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Single Wall Spill Bucket 5/1/2024 5/1/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 5/19/2026
Tank Fiberglass Single Wall Precision Test (Tank) Pass 5/19/2026

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 11

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found