Owner Summary
Click for Facility/Tank Ownership history
| Owner Number |
Owner Name |
Owner Status |
Purchase Date |
| U0038782 |
M & A Precision Truck and Auto Repair, Inc. |
Current Owner |
4/7/2017 |
| U0038748 |
MAH Holdings, LLC |
Former Owner |
4/7/2017 |
| U0034159 |
Athans Company |
Former Owner |
6/1/2004 |
| U0022023 |
Paul Moser Trucking |
Former Owner |
12/14/1993 |
Notice of Violations (Current)
NOV Number:
E0020261813
(Pending)
Issue Date:
7/15/2026
Expiration Date:
9/13/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs or dispensers. Perform test, complete form (form is available at www.sfm.illinois.gov) and maintain most current 2 years on site with other annual testing documentation. |
| 1 |
Annual leak detection certification not completed (Required annually). - Annual leak detection certification (interstitial sensors/ATG) not completed. Testing shall be completed and submitted to OSFM. |
| 1 |
Annual leak detection certification not completed (Required annually). - Annual leak detection certification (leak detectors and/or interstitial sensors) not completed. Testing shall be performed. |
| Facility |
Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and 2 years documentation maintained on site. |
| 1 |
Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Provide documentation that annual testing of all shear valves has been conducted and passed. Must maintain most current 2 years of inspection reports. |
NOV Number:
E0020261834
(Pending)
Issue Date:
7/16/2026
Expiration Date:
9/14/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Submit Notification Form for Ownership Change - Per 41 Ill. Adm. Code 176.440(g), a change in ownership information must be reported on an electronic Notification for Underground Storage Tank form, within 30 days of the change. The Notification Form is available at https://webapps.sfm.illinois.gov/USTPortal/NotificationForm . |
IEMA Numbers Associated with the Facility
No IEMA Numbers Found
LUST
Fund Eligibility and Deductibility Determinations
No Applications Found
Tank Number 1
| Capacity: |
12000 |
|
Petroleum Use: |
|
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
6/23/1994 |
|
Abandoned Material: |
|
| Current Age: |
32 |
|
Abandoned Date: |
|
| Install Date: |
12/14/1993 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
12/20/1993 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Composite Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
7/2/2025 |
7/2/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Incon TS 550 with SCALD |
7/2/2025 |
7/2/2026 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
7/2/2025 |
7/2/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
3/15/2024 |
3/15/2027 |
|
Piping
|
Flexible Double Wall A.P.T. Poly Tech P175SC |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
3/8/2024 |
3/8/2027 |
Leak Detect - Piping
|
Sump Sensor |
3/8/2024 |
3/8/2027 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
3/8/2024 |
3/8/2027 |
|
Tank
|
Composite Double Wall Modern Welding Glasteel II |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall A.P.T. Poly Tech P175SC
|
Precision Test (Piping)
|
Pass
|
7/2/2025
|
|
Tank
|
Composite Double Wall Modern Welding Glasteel II
|
Precision Test (Tank)
|
Pass
|
5/20/2024
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
Dispenser Information
Name\ID 1/2
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found