Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2032478
Status: Active
Facility Name: Aurora Mobil
Address: 300 South Broadway Aurora, IL 60525
County: Kane
Property Parcel: 15-27-106-001
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z000214
Green Tag Issue Date: 6/13/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: Izaan Management, Inc.
Owner Address: 300 S. Broadway Aurora, IL 60525
Owner Status: Current Owner
Purchase Date: 5/27/2021
Type of Financial Responsibility: Designated Savings Account
Financial Responsibility Reporting Due Date: 2/8/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0040511 Izaan Management, Inc. Current Owner 5/27/2021
U0031450 M N M, Inc. Former Owner 1/1/2002
U0022857 Mohi Inc Former Owner 2/24/1994
U0021985 Chaudhary Mohammad Y Former Owner 12/31/1967
U0028884 M & J Business Inc Former Owner

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
01058-2026UPG Upgrade Approved / Issued 9/2/2026 9/2/2026 3/3/2027 Documents
01039-2026REM Removal Cancelled by Contractor 8/28/2026 8/31/2026 3/3/2027 Documents
01057-2026REM Removal Approved / Issued 9/1/2026 9/2/2026 3/3/2027 Documents

Notice of Violations (Current)

NOV Number: E0020261579 (Pending)    Issue Date: 6/17/2026    Expiration Date: 8/16/2026    View NOV Form

Tanks Violations
3 Miscellaneous - Vapor caps need to be replaced. They are not functioning.
4 Miscellaneous - Premium STP sump sensor is lying down on the bottom of the sump.
4 Miscellaneous - Vapor caps need to be replaced. They are not functioning.
3, 4 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
3 Stick inserted in drop tube overfill device rendering it inoperative - Remove stick.
3, 4 Tank monitor does not appear to function properly and requires maintenance. - ATG is in warning alarm Software Module Warning. CSLD tank testing is not functioning.
3, 4 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Both STP and all UDC sumps need triannual testing.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
99-2700 2/17/2000 Removal Log 03702-1999REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
99-2700 Eligible 3/14/2000 3/23/2000 $15,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 2/17/2000
OSFM First Notify Date: 9/2/1993 Abandoned Material:
Current Age: 32 Abandoned Date:
Install Date: 1/1/1968 Red Tag Issue Date:
Last Used Date: 12/7/1999 Fee Due: $0.00
Product Date: 1/1/1968

Equipment Information

No Equipment Listed


Additional Tests

No Tests Listed




Tank Number 2

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 2/17/2000
OSFM First Notify Date: 9/2/1993 Abandoned Material:
Current Age: 32 Abandoned Date:
Install Date: 1/1/1968 Red Tag Issue Date:
Last Used Date: 12/22/1998 Fee Due: $0.00
Product Date: 1/1/1968

Equipment Information

No Equipment Listed


Additional Tests

No Tests Listed




Tank Number 3

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/14/2000 Abandoned Material:
Current Age: 26 Abandoned Date:
Install Date: 2/24/2000 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 2/29/2000

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 3/3/2026 3/3/2027
Leak Detect - Tank Automatic Tank Gauging Red Jacket Pro Plus with CSLD 3/3/2026 3/3/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 3/3/2026 3/3/2027
Overfill Prev Device Overfill Drop Tube Valve 2/6/2024 2/6/2027
Piping Flexible Double Wall Total Containment Enviroflex non-corrosive Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump 8/11/2026 8/11/2029
Leak Detect - Piping Sump Sensor with positive shutdown 8/11/2026 8/11/2029
Spill Contain Device Single Wall Spill Bucket 2/6/2024 2/6/2027
Tank Fiberglass Double Wall XERXES Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Total Containment Enviroflex non-corrosive Precision Test (Piping) Pass 3/3/2026
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 2/13/2020



Tank Number 4

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/14/2000 Abandoned Material:
Current Age: 26 Abandoned Date:
Install Date: 2/25/2000 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 2/29/2000

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 3/3/2026 3/3/2027
Leak Detect - Tank Automatic Tank Gauging Red Jacket Pro Plus with CSLD 3/3/2026 3/3/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 3/3/2026 3/3/2027
Overfill Prev Device Overfill Drop Tube Valve 2/6/2024 2/6/2027
Piping Flexible Double Wall Total Containment Enviroflex non-corrosive Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump 8/11/2026 8/11/2029
Leak Detect - Piping Sump Sensor 8/11/2026 8/11/2029
Spill Contain Device Single Wall Spill Bucket 2/6/2024 2/6/2027
Tank Fiberglass Double Wall XERXES Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Total Containment Enviroflex non-corrosive Precision Test (Piping) Pass 3/3/2026
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 2/20/2020

Failed test = the latest test has failed.

Not applicable = a test does not apply to this equipment type or configuration.

No passing test found = a passing test is expected but was not found from the source data.


Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 8/10/2021 8/10/2024
Leak Detect - Piping Sump Sensor 3/3/2026 3/3/2027



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 8/11/2026 8/11/2029
Leak Detect - Piping Sump Sensor 3/3/2026 3/3/2027



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 8/10/2021 8/10/2024
Leak Detect - Piping Sump Sensor 3/3/2026 3/3/2027



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 12/14/2022 12/14/2025
Leak Detect - Piping Sump Sensor with positive shutdown 3/3/2026 3/3/2027

Failed test = the latest test has failed.

Not applicable = a test does not apply to this equipment type or configuration.

No passing test found = a passing test is expected but was not found from the source data.